Can You Get Shocked by a Megger?

You felt a jolt while insulation testing, or you are about to use a megger for the first time and want to know how dangerous it is. The output is current limited, but that is not the whole story.

As an Amazon Associate, Akermin earns from qualifying purchases. Product links on this page are affiliate links.

You can get a shock from an insulation tester, and it hurts. During a test the leads carry hundreds or thousands of volts DC, and although the current is limited to a few milliamps on most instruments, touching a probe or the equipment under test gives a sharp jolt that can throw you off a ladder. The more serious danger comes afterwards: cables, motors and capacitors store charge at the test voltage and can deliver a much bigger shock if you touch them before they are discharged, and a tester connected to a circuit that was not properly isolated exposes you to mains voltage as well.

Three different ways a megger test can shock you

It helps to separate the hazards, because each one has its own control.

Source When it happens How serious Control
Tester output during the test Touching a probe tip, a clip or the conductor under test while the button is pressed Painful, usually not lethal from a handheld unit, but can cause falls and burns Hands off everything during the test; use clips, not hand-held probes, for long tests
Stored charge after the test Disconnecting leads too early or touching a long cable, large winding or capacitor Can be dangerous, especially on long cables and high-voltage tests Wait for auto-discharge; earth the item for at least the test duration
Mains or another live source Circuit was not isolated, was back-fed, or a neutral was shared Potentially lethal Lock out, prove dead before connecting
Induced voltage Long cables running beside live circuits pick up voltage Can be significant on long parallel runs Earth the cable before and after testing; specialist practice for HV routes

People often say the current is too small to hurt you. That is true of the steady current from a handheld unit, but it ignores the stored-energy and live-circuit hazards, which cause most of the real injuries.

Why the current is limited, and what that does not cover

An insulation tester is designed to measure leakage in microamps through insulation that is hundreds of megohms. It does not need much current, so its high-voltage converter is built to supply only a small amount. Into a short circuit, most handheld testers can push only a milliamp or so, and the output voltage collapses toward zero. The instrument standard IEC 61557-2 requires the meter to deliver at least 1 mA at its nominal voltage at the minimum acceptable resistance, and it limits how much current the tester may supply.

Your body has a resistance of the order of a thousand to a few thousand ohms hand to hand once the skin breaks down, so at 500 or 1,000 V you will take whatever current the meter can give. A milliamp or two at that voltage, together with the sudden discharge of any charge already on the circuit, produces a strong, sharp reaction. It is the reflex, not the current, that usually causes harm: a hand hitting a sharp edge, a fall from steps, or a dropped tool into live gear.

High-voltage testers for cables and medium-voltage plant generate 5 kV, 10 kV or more and can supply more current. Treat those as a high-voltage hazard, used only by trained, authorized people within an exclusion zone.

Stored charge: the hazard people underestimate

Conductors separated by insulation form a capacitor. A short cord has almost no capacitance, but a long run of cable, a large motor winding, a transformer or a power factor capacitor bank can hold a significant charge at the test voltage. When the button is released, that energy stays in the equipment until it is drained.

Modern testers discharge the circuit through an internal resistor when the test ends, and the display shows the voltage falling. If you pull the leads off before it reaches near zero, the charge stays put. Worse, insulation shows dielectric absorption: after being discharged briefly, it can slowly rebuild a voltage from charge stored deep in the material. This is why high-voltage cable is kept earthed after testing, not just discharged once.

  • Keep the leads on until the meter reads near zero volts.
  • For long cables and large machines, apply an earthing lead or discharge stick for at least as long as the test lasted, and longer after high-voltage tests.
  • Leave temporary earths in place until reconnection.
  • Use a voltage tester to confirm zero before handling conductors.

How to test without getting shocked

  1. Isolate and lock out the circuit using your site procedure. Remove fuses or open breakers and apply a lock.
  2. Prove dead with a separate, rated voltage tester, checked on a known live source before and after. Many insulation testers will refuse to test and warn if they detect voltage, but do not rely on that alone.
  3. Disconnect electronics, capacitors and surge devices from the circuit, both to protect them and to avoid charging capacitors to the test voltage.
  4. Connect the earth lead first to a good earth point, then the line lead to the conductor. Use crocodile clips so your hands are not on the probes.
  5. Warn others and guard the far end of any cable. Someone at the other end of a run can be shocked by your test.
  6. Press test and keep hands clear. Use the lock or remote button if the meter has one.
  7. Release and wait for automatic discharge, then remove the line lead first and the earth lead last.
  8. Inspect your leads regularly. Cracked insulation on a lead is a direct path to your hand at the test voltage.

A combined tester such as the Kyoritsu KEW 6010B includes a voltage measurement function, which helps, but a dedicated voltage tester for proving dead remains good practice. For a broader view of instruments and their safety features, see insulation resistance testers.

If you were shocked, and when to get help

A brief jolt from a handheld tester during a test usually leaves nothing more than a sting. Seek medical advice if you have a burn, numbness, tingling that persists, chest pain, palpitations, or if the shock came from stored charge in a large machine or high-voltage cable, or from mains. Electrical injuries can cause internal damage that is not visible on the skin.

Then find out why it happened. If the shock was from the circuit rather than the meter, your isolation failed and needs investigating before anyone works there again. If it came from stored charge, revise the discharge step. On solar arrays, remember that modules keep producing voltage in daylight; insulation testing there needs a purpose-built approach, described in the guide to solar insulation testers. Work on medium-voltage equipment or anything you cannot safely isolate should go to a qualified electrician or testing contractor.

Make discharge part of every test

Before your next test, set a habit: earth lead on first, clips not probes, hands off during the test, and leads left connected until the display shows near zero volts. On anything longer than a short circuit run or larger than a small motor, add a separate earthing lead for at least the test duration before you touch a conductor.

Frequently Asked Questions

Can a megger shock kill you?

A brief shock from a handheld insulation tester's output is very unlikely to be fatal, but it is not risk free, and secondary injuries from falls are real. Stored charge in large equipment and contact with mains through poor isolation are far more dangerous.

Why did I get shocked after the test finished?

The cable or winding stored charge at the test voltage and you touched it before it was fully discharged, or the insulation rebuilt some voltage through dielectric absorption. Keep leads connected until the meter shows near zero, and earth large items.

Is a hand-crank megger more dangerous than a digital one?

The output hazard is similar, but older crank units usually lack automatic discharge and live-circuit warnings. You must discharge the item yourself with an earthing lead after every test.

Do insulating gloves help?

Rated insulating gloves add protection, and they are required for some high-voltage work. They do not replace safe isolation, discharge and keeping hands off the circuit during the test.