A megger uses DC. Whether it is an old hand-cranked unit or a modern battery tester, it applies a steady direct voltage, typically 250, 500 or 1,000 V and up to 5 kV or more on larger models, between the conductor and earth and measures the leakage current. DC is used because cables and windings act like capacitors: with AC, a large charging current would flow continuously and hide the tiny leakage current, while with DC that charging current dies away in seconds. AC insulation tests do exist, but they are withstand tests done with different equipment, not a megger.
How the DC is produced inside the meter
The original insulation testers used a hand-cranked DC generator, a small dynamo with a commutator, often with a slipping clutch so the output stayed near its rated voltage once the handle reached speed. Some crank units produced AC internally and rectified it. Either way, the voltage reaching the test leads was DC.
Modern testers run on batteries. An electronic converter switches the low battery voltage at high frequency, steps it up through a small transformer, rectifies it and smooths it to a steady DC output at the selected voltage. A feedback loop holds the voltage near the nominal value as the load changes. So although there is AC inside the converter, what the insulation sees is DC.
The polarity is usually fixed. On many testers the line terminal is negative with respect to earth. Check your manual if the polarity matters for your test, for example when testing cables where the result can depend slightly on polarity.
Why DC gives a readable insulation measurement
Any two conductors separated by insulation form a capacitor. With DC applied, current flows in three components:
| Current component | What causes it | How it behaves with DC |
|---|---|---|
| Capacitive charging current | Conductor and earth charge up like capacitor plates | Large at first, falls to almost zero in seconds |
| Absorption (polarization) current | Molecules in the insulation align with the field | Falls slowly over minutes |
| Conduction (leakage) current | Real current through and across the insulation | Steady; this is what reveals moisture, dirt and damage |
Under DC, after a minute or so, the first two have faded and the leakage current is left. The meter divides voltage by current and shows megohms. With AC, the capacitor charges and discharges on every cycle, so the capacitive current never stops. On a long cable it can be many times larger than the leakage, and the meter would be measuring cable capacitance, not insulation quality.
DC also allows the timed tests that make insulation testing useful. The polarization index, the ten-minute reading divided by the one-minute reading, and the dielectric absorption ratio, the sixty-second reading over the thirty-second reading, both rely on watching the absorption current fade under steady DC. A ratio around 2 or more on a polarization index suggests clean, dry insulation; close to 1 suggests leakage is swamping everything.
A rough calculation shows the scale of the problem with AC. A long cable with a capacitance of 0.5 microfarads to earth, at 500 V and 50 Hz, would draw a capacitive current of about 2 pi times 50 times 0.5 microfarads times 500 V, which is roughly 79 mA. The leakage through healthy insulation of 500 MΩ at the same voltage is 1 microamp, nearly eighty thousand times smaller. No practical meter could pick that leakage out of the charging current, and a portable tester could not supply 79 mA at 500 V anyway. Under DC, the same cable draws a brief charging pulse and then settles to the leakage alone.
Where AC testing comes in instead
AC tests are used for insulation, but they answer a different question and use different instruments.
- AC withstand or hipot tests apply a high AC voltage for a fixed time to prove the insulation does not break down. This is common in factory testing of appliances, switchgear and transformers. The result is pass or fail, not a resistance in megohms.
- Very low frequency (VLF) testing applies AC at a fraction of a hertz to long medium-voltage cables. The low frequency keeps the charging current manageable while still stressing the insulation in a way closer to service conditions than DC.
- Tan delta or dissipation factor testing measures insulation losses under AC to assess aging in cables, bushings and transformers.
For routine maintenance, commissioning of low-voltage wiring and motor checks, the DC insulation resistance test is the standard tool. Medium-voltage cable owners often combine a DC insulation resistance test with VLF withstand or tan delta testing, since high DC voltage on some aged cable types is discouraged.
Using DC insulation testing correctly
- Isolate and prove dead. A DC test voltage on top of live AC mains gives meaningless readings and endangers you and the meter. Lock out and prove dead with a voltage tester first.
- Disconnect electronics. DC at 500 V or 1,000 V can damage drives, LED drivers, surge protectors, electronic breakers and smart controls.
- Pick the voltage that matches the equipment rating and your standard, commonly 500 V DC for 120 to 400 V circuits and motors.
- Hold the test long enough. A spot reading after one minute lets charging current fade. Short tests on long cables read low simply because the cable is still charging.
- Discharge afterwards. Because the test is DC, the cable or winding is left charged. Wait for the meter’s automatic discharge, and earth large items for at least the test duration.
Installation testers such as the Kyoritsu KEW 6010B or the Srliya insulation and RCD tester apply DC on their insulation ranges and use separate methods for loop and RCD tests, which use the mains itself. Those mains-based tests are why such meters must be selected to the correct function before connecting. For more on choosing a tester, see insulation resistance testers.
How an insulation tester differs from other DC meters
A multimeter’s ohms range also uses DC, but only a few volts and a much higher current relative to what it measures. It is built for low and mid-range resistance, not for hundreds of megohms under stress. A milliohm meter, also DC, goes the other way and measures tiny resistances in windings and joints with four-wire connections, as described in milliohm meters for low resistance testing. A low-voltage continuity test proves a conductor is connected; an insulation test proves conductors are separated. The two are compared in insulation tester versus continuity test.
So a DC test from a megger, a multimeter and a milliohm meter are three different measurements, and none substitutes for the others.
Run a timed DC test next
On your next motor or cable, hold the DC test for a full ten minutes and record the readings at thirty seconds, one minute and ten minutes. The ratios between them tell you far more about the insulation than a single spot value, and they only work because the test is DC.
Frequently Asked Questions
Is a megger reading affected by the AC mains frequency?
Not if the circuit is isolated as it should be. If there is induced AC on a long cable near live circuits, readings can be unstable, and the cable should be earthed and tested with proper procedures.
Why is DC used instead of AC for insulation testing?
With DC the capacitive charging current dies away, leaving the small leakage current that shows the insulation's condition. With AC the charging current flows continuously and masks it.
Can DC testing damage AC cables?
Normal DC insulation resistance tests at the correct voltage are routine on low-voltage cables. On some aged medium-voltage polymer cables, high DC withstand voltages are discouraged and AC or VLF methods are preferred.
Do crank meggers produce DC too?
Yes. The generator produces DC, or produces AC that is rectified inside, so the leads deliver DC.