Most standing-pilot gas water heaters fail in one of three ways. If the pilot will not light, the gas supply, the igniter or a clogged pilot tube is usually to blame. If it lights but goes out when you release the button, the thermocouple is not making enough voltage, which a multimeter on DC millivolts confirms. If it lights and runs but keeps going out, look at a dirty flame arrestor or air intake screen, drafts, or a thermal cutoff that has tripped. Follow the lighting label exactly, test the thermocouple, and call a plumber or gas technician if a safety switch has tripped or you smell gas.
Inside the burner compartment
A conventional tank water heater has a gas control valve on the outside of the tank and a sealed burner compartment at the bottom. The pilot is a small, constant flame. A thermocouple sits in that flame and produces a small DC voltage that holds a safety magnet open in the gas valve. If the pilot goes out, the voltage drops, the magnet releases, and gas stops.
Most heaters sold in North America for many years are flammable vapour ignition resistant, often marked FVIR. They have a sealed combustion chamber, a flame arrestor plate or screen at the base that air must pass through, and a thermal cutoff that shuts the gas if the chamber gets too hot, as it would if flammable vapour ignited or airflow became blocked. Those features prevent fires in garages, but they also add causes of a dead pilot. Some newer heaters replace the thermocouple with a thermopile and an electronic control that shows a status light; on those, the light’s blink pattern explains the fault.
Pilot symptoms and what they point to
| Symptom | Likely cause | Next step |
|---|---|---|
| No spark when pressing the igniter | Faulty piezo igniter or loose wire | Watch through the window in a dark room; replace igniter |
| Spark but no flame | Gas valve off, supply off, air in line, blocked pilot tube | Check gas supply; hold pilot button longer |
| Lights but goes out when button is released | Weak or loose thermocouple, or small pilot flame | Millivolt test; check thermocouple nut at valve |
| Runs for hours or days, then goes out | Dirty flame arrestor or intake screen, drafts, debris | Vacuum the intake screen; check for drafts |
| Will not relight at all after going out, no obvious cause | Thermal cutoff tripped | Professional inspection |
| Status light blinking on an electronic valve | Fault code from the control | Look up the code on the heater label or manual |
Relighting by the label
- Find the lighting instructions on the label on the tank. Follow those over any general advice; designs differ.
- Set the control knob to off and wait at least five minutes, or the time stated, so any gas can clear.
- Check that the gas shutoff on the supply pipe is open and, if other gas appliances work, that gas is reaching the house.
- Turn the knob to pilot. Press and hold the pilot button, then press the igniter repeatedly while watching through the sight glass.
- Once the pilot lights, keep holding the button for the time the label gives, often a minute, so the thermocouple heats up.
- Release slowly. If the pilot stays lit, turn the knob to on and set the temperature. The main burner should light.
If the heater has been off for a long time, it may take a minute or two of holding the button before gas reaches the pilot and it lights.
Measuring the thermocouple
A thermocouple either produces enough millivolts or it does not, so a multimeter with a DC millivolt range gives a clear answer. Many modern FVIR heaters have the thermocouple sealed into the burner assembly; on those, the thermocouple is replaced as part of the pilot assembly, and a technician should do it.
- Where the thermocouple connects to the gas valve with a nut, unscrew the nut with the gas knob off.
- Relight the pilot and keep the pilot button held down throughout; with the thermocouple disconnected, the valve only passes pilot gas while you hold it.
- Touch one meter lead to the end of the thermocouple and the other to its copper tube. A healthy thermocouple in a good pilot flame commonly reads in the region of 20 to 30 millivolts. Readings far lower mean the thermocouple is worn or the flame is not hitting it properly.
- Look at the flame. It should be steady, mostly blue, and wrap around the top of the thermocouple. A small or yellow flame means the pilot orifice or air intake is dirty.
- Reconnect the nut snugly. A loose nut loses voltage at the connection and gives the same symptom as a failed thermocouple.
A loaded reading, taken with an adapter while the thermocouple stays connected, is lower than the open reading; the valve maker publishes its dropout figure. If the thermocouple tests well and the pilot still drops out, the magnet in the gas valve may be failing, which means a new valve fitted by a professional.
Pilots that keep going out
On FVIR heaters the most common cause of a pilot that dies every few days is a clogged air intake. Lint, dust and pet hair build up on the screen or arrestor plate around the base of the tank, especially in laundry rooms and garages. The burner starves for air, the flame lifts or weakens, and the thermocouple cools. With the heater off, vacuum around the base and any visible intake screen. Do not remove sealed covers or plates unless the manual says you can.
Other causes include drafts from a nearby door or fan, a blocked flue or poor venting that lets combustion gases spill back, and condensation dripping onto the pilot on cold mornings. If the flue hood above the tank feels hot or you see soot or scorching around the top or bottom of the heater, venting is suspect, and that is a carbon monoxide hazard.
Safety limits and when to get help
If you smell gas, do not try to light anything, do not operate switches, leave the house and call the gas utility from outside. Call a licensed plumber or gas technician if the thermal cutoff has tripped, because that means the burner chamber overheated and the cause needs finding; if you see scorching, soot or melted parts; if the pilot will not light with gas confirmed on; or if a new thermocouple does not fix it. A water heater in a garage or near stored fuels, paints or solvents needs those stored elsewhere before relighting. Keep a working carbon monoxide alarm near any gas appliance and on each sleeping level.
Before you call anyone
Turn the knob off, wait five minutes, and relight using the label on the tank while holding the pilot button for a full minute. If it will not stay lit, vacuum the air intake around the base and test the thermocouple on the millivolt range; if it still fails, or anything looks scorched, call a plumber or gas technician.
Frequently Asked Questions
Why does my water heater pilot go out every few days?
A clogged air intake screen or flame arrestor is the most common cause on modern heaters. The pilot starves for air, weakens and goes out. Drafts and venting problems are the next things to check.
How do I know if the thermocouple is bad?
If the pilot lights but goes out as soon as you release the button after a full minute of holding, the thermocouple is the usual suspect. A multimeter reading far below the typical 20 to 30 millivolt range in a good flame confirms it.
What is the thermal cutoff on a water heater?
It is a safety device in the burner chamber of FVIR heaters that shuts the gas if the chamber gets too hot. Once tripped, it typically has to be replaced. Because it signals overheating, a professional should find the cause.
Can I relight a water heater pilot myself?
Yes, homeowners routinely relight pilots by following the label on the tank. Replacing gas parts is different and often regulated, so leave valve and burner work to a qualified person.
My water heater has a blinking light instead of a pilot button. What now?
That is an electronic gas control. The blink pattern is a fault code; the label on the heater or the manual explains each pattern. Common ones point to a weak thermopile, a tripped cutoff or a dirty intake.