How to Check Insulation Resistance

You suspect a cable, motor or circuit has damaged insulation, an RCD keeps tripping, or you need to prove new wiring is sound. Here is how to run an insulation resistance test safely and judge the result.

As an Amazon Associate, Akermin earns from qualifying purchases. Product links on this page are affiliate links.

You check insulation resistance with an insulation resistance tester, often called a megger, which applies a DC test voltage much higher than a multimeter’s, commonly 250, 500 or 1000 volts, and reports resistance in megohms. The circuit must be isolated and proven dead first, and anything electronic that could be damaged by the test voltage must be disconnected. Test between each conductor and earth and between the conductors, then compare the readings with the minimum your local wiring rules or the equipment maker requires. Very high readings mean sound insulation; low or falling readings point to moisture, contamination or damage.

Why a multimeter cannot do this job

Good insulation has resistance in the hundreds or thousands of megohms. A multimeter’s ohms range uses a few volts at most, which is not enough to stress the insulation or to reveal weak points that only conduct when pushed. Damage often looks perfect at low voltage: a nicked conductor sitting close to an earthed box, a damp joint, carbon tracking in a motor winding. At the test voltage of an insulation tester, those weak paths start to leak current, and the tester reads that leakage as a lower resistance.

A continuity test answers a different question: is this conductor connected end to end? An insulation test asks whether the conductors are kept apart from each other and from earth. The two are complementary, as covered in insulation testing versus continuity testing.

Choosing the test voltage

The test voltage is chosen from the circuit’s working voltage, so the insulation is stressed beyond normal use without being overstressed. Local wiring regulations and equipment manuals set the exact values; the table shows common practice, not a substitute for your local rule.

What you are testing Common DC test voltage Typical acceptance approach
Extra-low voltage and signalling circuits 250 V Minimum set by local regulations, lower than for mains
Household and light commercial circuits up to about 500 V 500 V Many regulations require at least 1 megohm; healthy new wiring is usually far higher
Circuits and equipment rated up to about 1000 V 1000 V Per regulation or equipment maker
Motors and generator windings Chosen from the machine’s voltage rating Compare against maker data, a standard such as IEEE 43, and the machine’s own history
Solar PV strings Per PV testing standard and module rating Per installation standard; use a tester designed for PV

Installation testers combine insulation testing with other checks used in electrical installation work: the KYORITSU KEW 6010B multifunction tester covers continuity, insulation, loop and RCD tests, and the digital insulation tester with RCD and loop test pairs insulation testing with RCD and loop functions. For PV systems, see solar insulation resistance testers, and for general options, insulation resistance testers.

Running the test step by step

  1. Isolate and lock off. Switch off and lock out the supply at the breaker or isolator, and tag it. Prove dead with an approved voltage tester, testing the tester on a known live source before and after.
  2. Disconnect sensitive loads. Unplug appliances and remove or disconnect anything with electronics: dimmers, smart switches, LED drivers, surge protectors, timers, electronic RCDs, motor drives and smoke alarms. These can be damaged by the test voltage or will drag the reading down. Remove lamps.
  3. Check the tester. Short the leads and press test on the insulation range; it should read near zero. Separate the leads; it should read above its maximum range.
  4. Line and neutral to earth. On a single-phase circuit, you can link line and neutral together and test between them and earth. This checks both conductors in one go.
  5. Line to neutral. Test between line and neutral with loads removed. For three-phase, test each phase to each other phase and each to earth.
  6. Hold the test long enough. Press and hold until the reading stabilises, usually a few seconds on small circuits, longer on long cables and motors where cable capacitance must charge.
  7. Let the tester discharge. Keep the leads connected after releasing the button until the tester shows the voltage has dropped. A long cable or motor can hold a dangerous charge.
  8. Record results with the test voltage, temperature and humidity, so future tests can be compared.
  9. Reconnect everything and verify the circuit works before restoring normal use.

Making sense of the number

Readings above the tester’s top range, shown as a greater-than symbol, are what you expect from healthy wiring. A reading that is above the regulatory minimum but much lower than similar circuits nearby deserves a closer look. Insulation resistance falls as temperature and humidity rise, so a damp morning or a warm motor reads lower than a dry cold one; compare like with like.

For motors and large cables, the trend is more useful than any single figure. Technicians also use the polarization index: the ratio of the reading at ten minutes to the reading at one minute. Clean, dry insulation keeps rising as it polarises, giving a ratio well above one; a ratio close to one suggests moisture or contamination. To localise a low result, split the circuit at junction boxes and test each section. If a low reading disappears when a section is disconnected, the fault is in that section.

A few patterns come up often. A reading that is low only between line and earth, while line to neutral is fine, often points to a damaged cable sheath against a metal box, a screw through a cable, or water in an outdoor fitting. Low readings on every circuit in a building after a flood or a long unheated period usually mean moisture, and they often improve as the building dries. A result that is fine with all loads unplugged but low when one appliance is connected points to that appliance, commonly a heating element, a washing machine or an outdoor tool. Neutral-to-earth faults are easy to miss because they rarely blow a fuse, yet they are a frequent cause of RCD trips.

Safety boundaries and when to call an electrician

An insulation tester produces a voltage high enough to shock, and the circuit under test can store charge after the test. Never test a live circuit; most testers warn if voltage is present, but do not rely on that. Keep hands off conductors while testing, and warn anyone else working nearby. Work on fixed mains wiring is regulated in many places and must be done or certified by a qualified electrician. A low result on a cable inside walls, in consumer units, or on equipment connected to a supply you cannot isolate is a job for a licensed electrician. For low-resistance checks such as bonding and joints, a different tool applies; see milliohm meters for low resistance.

Start with the circuit that trips

If an RCD keeps tripping, isolate that circuit, unplug everything on it, and run a 500 volt line-and-neutral-to-earth test; then plug loads back in one at a time on a working circuit to see whether the wiring or an appliance is leaking to earth.

Frequently Asked Questions

What is a good insulation resistance reading?

Healthy wiring usually reads in the hundreds of megohms or above the tester's range. Many regulations set a minimum of around 1 megohm for 500 volt tests on low-voltage circuits, but you should follow your local rule and the equipment maker's figure.

Can I test insulation resistance with a multimeter?

Not properly. A multimeter uses too little voltage to reveal weak insulation, so it can show an open circuit on cable that would fail a real insulation test.

Why does my insulation reading keep climbing during the test?

The cable or winding is charging like a capacitor and the insulation is polarising. A steady rise is normal and is a good sign; hold the test until it stabilises.

Will an insulation test damage my appliances?

It can damage electronics such as dimmers, LED drivers and surge protection devices. Disconnect them before testing the circuit.

Does humidity affect insulation resistance?

Yes. Moisture on surfaces and inside insulation lowers the reading. Record conditions so you can compare results fairly over time.