The micron number is absolute pressure, so it counts down as the pump works: atmospheric pressure is about 760,000 microns and a well-evacuated system sits at a few hundred. Until the pressure falls into the gauge’s micron range the display shows an over-range indication or a vacuum figure in inches of mercury, and only then does it switch to microns. Aim for below about 500 microns, close the valve between pump and system, and watch for several minutes: a reading that rises slightly then levels off well under about 1,000 microns passes, a slow climb that flattens higher means moisture, and a steady climb that never stops means a leak.
What a micron actually is
A micron in HVAC work is a micron of mercury, one thousandth of a millimetre of mercury, a unit of absolute pressure. That word absolute matters. A normal refrigerant gauge shows pressure relative to the air around you, so it reads zero with the hoses open. A micron gauge reads from a perfect vacuum upwards, so a smaller number means less gas, and less water vapour, left inside the system.
| Condition | Microns | Other units |
|---|---|---|
| Sea level atmosphere | About 760,000 | 760 Torr, about 29.92 inHg |
| One inch of mercury | 25,400 | 25.4 Torr |
| One Torr | 1,000 | 1 mmHg |
| Common evacuation target | 500 or lower | 0.5 Torr |
| Typical decay test ceiling | About 1,000 | 1 Torr |
That table explains why a compound gauge needle near 30 inches of vacuum tells you almost nothing about dryness. The last inch of mercury contains 25,400 microns of range, and the part that matters for removing moisture is the bottom few hundred. Water boils at very low temperatures at those pressures, which is the whole point: the pump lowers the pressure until any water in the system boils off as vapour and gets pulled out.
Where the micron number appears on Fieldpiece tools
Fieldpiece shows vacuum in two common ways. Many of the digital manifolds in the SMAN family include a built-in vacuum sensor, so the manifold screen shows a micron reading during evacuation. The wireless vacuum probes, part of the Job Link family, sit on the system and send the reading to a manifold or the phone app. Either way, the reading behaves the same.
- Above the micron range. When you first start the pump, the pressure is far too high for a micron sensor. The display shows an over-range indication, dashes, or a vacuum figure in inches of mercury, depending on model and settings. That is normal.
- Entering range. As the system gets close to a deep vacuum, the micron figure appears and starts falling quickly.
- The slow stretch. Below a few thousand microns the drop slows down sharply. This is where moisture is boiling off and where most of the job’s time goes.
- The target. The number creeps down below 500. On a clean, dry, tight system it can go well below that.
Check your units setting. Some tools can show Pascals, millibar or Torr instead of microns, and a reading of 0.5 Torr is the same as 500 microns. If the number looks absurdly small, check the units before you celebrate.
Getting a reading you can trust
Where the sensor sits changes what it reports. A micron sensor right at the pump reads the pump’s vacuum, which falls fast and looks great while the far end of the system is still wet. Use these habits:
- Mount the vacuum sensor on the system side, as far from the pump as practical, ideally on a service port with the core removed by a core removal tool.
- Use short, large-diameter hoses, or better, dedicated vacuum hoses, and remove the Schrader cores. The cores and thin hoses restrict flow far more than most people expect.
- Keep the sensor upright or as the manual describes, and do not let oil from the pump or the system get drawn into it. Oil contamination is the main reason micron sensors read high or erratically.
- Check hose and fitting seals. A worn gasket in a hose end can leak enough to stop you reaching target.
- Before a job, cap the sensor alone on the pump through a short connection. If it cannot pull the bare sensor below a few hundred microns quickly, the pump oil, the hose or the sensor is the problem, not the system.
The decay test: reading the number after the pump stops
The micron reading earns its keep after you reach target. Close the valve that isolates the pump from the system, so the sensor sees only the system, and watch it for at least ten minutes. Many installers turn the pump off at the same time.
| What the micron reading does | What it means | Next step |
|---|---|---|
| Rises a little, then holds well under about 1,000 | Tight and dry | Release refrigerant or break vacuum as the job requires |
| Rises quickly, then flattens at a few thousand | Moisture still boiling off | Reopen the pump valve and keep evacuating; warm the system if possible |
| Climbs steadily without levelling off, back toward atmosphere | A leak | Find the leak before you go any further |
| Jumps around by large amounts | Contaminated or failing sensor, loose connection | Clean or check the sensor, test on the pump alone |
For a leak, pressurise with dry nitrogen to a pressure the equipment is rated for and find it with soap solution or an electronic detector before you evacuate again. A heated diode or infrared detector, for example the Fieldpiece DR82 infrared leak detector, is used once there is refrigerant in the system; the reviews of the INFICON D-TEK 3 and the INFICON D-TEK Stratus explain how infrared and other detector types respond to small leaks. Never use oxygen or compressed air to pressure test a refrigeration system.
When the gauge, not the system, is at fault
Suspect the instrument when the bare sensor on a known-good pump will not go low, when two sensors on the same system disagree by thousands of microns, or when the reading changes with how you hold it. Micron sensors are delicate. Oil and refrigerant residue on the sensing element make it read high. Fieldpiece and other makers describe cleaning procedures for some sensors, typically with a suitable solvent, while others need returning for service. Follow the manual for your model rather than flushing it with whatever is in the van.
If you keep failing decay tests on new installations, check the pump oil, which absorbs moisture and loses performance fast, before you assume every system leaks. A pump with fresh oil, short vacuum hoses and cores removed should reach target readily on a tight, dry system.
On your next evacuation
Move the micron sensor to the far side of the system from the pump, pull the cores, and write down the reading every couple of minutes once it enters the micron range. When you hit 500 or below, isolate the pump and log the decay for ten minutes. That simple list of numbers is the evidence that the system is tight and dry, and it settles any later dispute about whether the evacuation was done properly.
Frequently Asked Questions
Why does my Fieldpiece gauge show dashes instead of microns?
The pressure is still above the micron range of the sensor, so it shows an over-range indication or a vacuum value in inches of mercury instead. Keep the pump running and the micron number appears as the system gets close to a deep vacuum.
Is 500 microns always the target?
It is the common target, but follow the equipment manufacturer's installation instructions, which sometimes specify a different figure. The decay test after isolating the pump matters as much as the lowest number reached.
Why does the reading drop fast at first and then stall?
That stall is usually moisture boiling off inside the system, or restriction from hoses and Schrader cores. Removing cores and using short, wide vacuum hoses speeds it up a lot.
Can I read microns with an analog compound gauge?
Not usefully. A compound gauge cannot resolve the last fraction of an inch of mercury where all of the useful vacuum range sits. A micron gauge is needed to judge dryness and run a decay test.
My micron reading rises after I close the valve. Is that a leak?
A small rise that levels off is normal. A reading that keeps rising steadily without flattening is the sign of a leak.