Turn the selector to the V with a wavy line above or beside it, written V~, VAC or ACV; the V with a straight and dashed line is DC and will not read household power correctly. Put the black lead in COM and the red lead in the V jack, never the A or mA jack. On a manual-ranging meter choose the lowest range that is still above the voltage you expect, for example 200 V for a 120 V supply or the 600 V or 750 V range for 230 V. Hold the probes by their insulated grips, black to neutral first, red to the live conductor, and read the RMS value on the display.
Finding AC on the dial
Alternating current reverses direction many times a second, 50 or 60 times depending on your country, so the meter has to measure it differently from a steady battery voltage. Manufacturers mark the AC voltage setting with a sine wave symbol, a tilde, next to the V. You will usually see one of these:
- V~ or a V with a wavy line on top: AC volts.
- VAC or ACV: AC volts, written out.
- V with a solid line over a dashed line: DC volts, the wrong setting for mains.
- mV~: millivolts AC, for small signals only.
- A~: AC current, which needs different jacks and is not for checking outlets.
Some meters have a single V position and a button that toggles AC and DC, often labelled SELECT or yellow. The display shows AC or a wave symbol when AC is active. Check it before every measurement, because many meters remember the last mode.
Setting it up and taking the reading
- Inspect the leads. No cracks, no exposed metal, finger guards intact. Leads and meter should be rated for the circuit, CAT II or better for outlets, CAT III for panels.
- Plug in the leads. Black to COM. Red to the jack marked V, often shared with ohms. If the red lead sits in the A jack and you touch a live outlet, you create a short through the meter.
- Turn the dial to V~. On an auto-ranging meter, that is all. On a manual-ranging meter, such as the Klein Tools MM325, pick a range above the expected voltage, the next step up from your supply.
- Test on a known live source first, if you have one, to prove the meter works before trusting a zero reading. Test a known live, then the unknown, then the known again for safety-critical checks.
- Connect one probe at a time. Black to neutral or the reference point, then red to the live conductor. Keep one hand away from the circuit where practical.
- Read the display. A 120 V outlet typically shows somewhere around 115 to 125 V; a 230 V supply commonly reads within a few percent either side of nominal.
- Remove red first, then black.
If you are working on household wiring for the first time, read our guide to choosing a multimeter for home electrical work, which covers CAT ratings and test lead safety.
Choosing the right range on a manual meter
| What you are measuring | Expected AC voltage | Typical manual range to choose |
|---|---|---|
| Doorbell or thermostat transformer | About 16 to 24 V | 200 V; a 20 V range would overflow on a 24 V transformer |
| North American outlet | About 120 V | 200 V |
| North American dryer or range circuit | About 240 V | 600 V or 750 V |
| UK, European, Australian outlet | About 230 V | 600 V or 750 V |
| Unknown supply | Not known | Highest AC range, then step down |
The number on each range is the maximum it can display. If the display shows OL or a 1 on the left, go up a range. Never exceed the meter’s maximum rated voltage, printed near the jacks.
Readings that look wrong, and why
A voltage on a wire that should be dead. Digital meters have a very high input impedance, so they can show tens of volts on a disconnected wire that runs beside a live one. This is capacitive coupling, not usable power. Our page on why ghost voltage appears on a multimeter explains how to tell the difference, including using a low-impedance mode where your meter has one.
Zero on a live outlet. Check the dial is on AC, not DC; check the red lead is in V, not A; check the leads are not broken. Also check that the outlet is not controlled by a wall switch or a tripped breaker or GFCI.
Odd readings on variable speed drives, dimmers or inverters. These produce distorted waveforms. Average-responding meters can read them inaccurately. A true-RMS meter reads the actual heating value of the waveform; see what true-RMS means on a multimeter.
Reading jumps or flickers. Usually poor contact in an outlet slot. Press the probe firmly against the metal contact inside the slot and hold steady.
Checking the meter is reading AC correctly
The easiest check is a second meter or a plug-in outlet voltage monitor on the same outlet at the same time. Two decent meters normally agree within a volt or two on a 120 V or 230 V supply. If you only have one meter, compare against a known live outlet, then measure the same outlet twice at different ranges on a manual meter; both readings should agree within the resolution of the lower range.
For low-voltage transformers, the label states the nominal secondary voltage. An unloaded transformer often reads a few volts higher than its label, which is normal and not a fault.
If the meter reads zero on a known live outlet even though the dial and jacks are correct, check the battery and the leads before anything else, then the AC function itself on a second known source. A meter that reads DC properly but not AC has an internal fault and should be replaced or sent for service, not used for safety checks.
Safety limits when measuring AC voltage
- Never measure mains AC with leads in the current jacks, and never switch the dial while probes are on a live circuit.
- Use a meter and leads rated for the location: CAT II covers outlets and plug-in appliances, CAT III covers distribution panels and fixed wiring.
- Do not work on panels, service entrances or North American 240 V appliance circuits unless you are trained. Call a licensed electrician for anything inside the breaker panel.
- Wet hands, wet floors and damaged leads make even a correct setting dangerous.
- A multimeter reading zero is not proof a circuit is safe to touch unless you proved the meter on a known live source before and after.
Prove the meter before you trust it
Set the dial to V~, put the leads in COM and V, and measure an outlet you know is live; once the display shows your normal supply voltage, you have the setting right and can move on to the circuit you actually need to check.
Frequently Asked Questions
What does the wavy line on a multimeter mean?
The wavy line, a sine wave or tilde, marks AC. V with a wavy line is AC voltage and A with a wavy line is AC current. The solid line with a dashed line beneath it marks DC.
Can I measure AC on the DC setting?
Not usefully. A DC setting averages the alternating voltage, which sits close to zero, so a live outlet may read near zero or a small fluctuating number. Always switch to AC for mains.
Which way round do the probes go for AC?
For AC the reading is the same either way round because the voltage alternates. Still, connect black to neutral or ground first and red to live, so the probe most likely to slip is the one on the safer conductor.
Why does my meter show 20 or 30 volts on a switched-off wire?