Ghost voltage is a reading of tens of volts on a conductor that is not connected to any source. It appears because a disconnected wire running alongside a live one forms a small capacitor with it, and a digital multimeter’s input impedance is so high (typically 10 MΩ) that the tiny current through that capacitance is enough to develop a voltage across the meter. The voltage is real but cannot deliver current; put any load on it and it collapses. A low-impedance (LoZ) mode or a solenoid tester loads the circuit and shows the true state.

The mechanism

Two parallel conductors separated by insulation are a capacitor. Fifty meters of cable with one live conductor and one disconnected conductor might have a few nanofarads between them. At 50 or 60 Hz that capacitance passes a few microamps. Through a 10 MΩ meter, a few microamps is a few tens of volts, so the display shows 40, 60 or 90 V. Through a lamp, a solenoid tester or a 3 kΩ LoZ input, the same few microamps produce millivolts. The wire is dead; only the meter’s sensitivity made it look alive.

Where it shows up

  • Spare or switched-off conductors in a multi-core cable or shared conduit.
  • Long runs of cable with one circuit isolated and its neighbors live.
  • Switch loops and traveler wires in lighting circuits.
  • Unused wires in junction boxes.
  • Disconnected equipment leads lying near live cables.

Ghost or real?

Observation Ghost voltage Real voltage
Reading with high-impedance meter Odd value: 30 to 100 V, often drifting Nominal value: 120 or 230 V, steady
Reading in LoZ mode Drops to near zero Stays at nominal
Solenoid tester No indication or faint Full indication
Small lamp connected Does not light Lights
Reading changes when a nearby circuit is switched Yes, often No

Proving a circuit dead

  1. Isolate at the breaker and lock or label it.
  2. Test the meter on a known live source to prove the meter works.
  3. Test the circuit with a LoZ mode or a solenoid tester. A high-impedance reading alone is not proof either way.
  4. Test the meter again on the live source.
  5. Only then treat the circuit as dead.

The order matters: ghost voltage tempts people to dismiss a reading as phantom, and a real 230 V conductor dismissed that way is how injuries happen. The low-impedance test resolves it in seconds, which is why meters intended for electrical work include one. See best multimeters for home and DIY for models with LoZ and what non-contact voltage detection is for the first-check tool.

Why not just use LoZ always?

Loading the circuit is exactly what electronics measurements must avoid; a LoZ input across a sensor or control circuit would disturb it and could damage it. High impedance is the right default for electronics; LoZ is the right tool for mains conductors. Meters with both let you choose. Related: why multimeter readings jump around.

Fluke 117 Digital Multimeter, Non-Contact AC Voltage Detection, Measures Resistance/Continuity/Frequency/Capacitance/Min Max Average, Automatic AC/DC Selection, Low Impedance Mode

Fluke 117 Digital Multimeter, Non-Contact AC Voltage Detection, Measures Resistance/Continuity/Frequency/Capacitance/Min

View on Amazon
Klein Tools MM420 Digital Multimeter, Auto-Ranging TRMS Multimeter, 600V AC/DC Voltage, 10A AC/DC Current, 50 MOhms Resistance

Klein Tools MM420 Digital Multimeter, Auto-Ranging TRMS Multimeter, 600V AC/DC

View on Amazon

Products shown because their documented specifications fit this guide. Price and availability are on Amazon and can change.

Frequently Asked Questions

Is ghost voltage dangerous?

The induced voltage itself cannot deliver meaningful current. The danger is misjudgment: assuming a reading is ghost voltage when the wire is actually live. Always prove dead with a low-impedance test.

What is LoZ on a multimeter?

A low-impedance voltage mode (typically a few kilohms) that loads the circuit slightly. Ghost voltage collapses to near zero; real voltage stays. Fluke 117, Klein and others include it.

Why does a non-contact tester also beep on a dead wire?

Some sensitive non-contact testers respond to the same coupled field. A tester with adjustable sensitivity, or confirmation with a LoZ meter or solenoid tester, resolves it.

Affiliate disclosure: Akermin earns a commission from qualifying Amazon purchases made through links on this page. Our editorial picks are based on documented specifications and owner feedback, not commissions.