How to Check a Megger Test in Cables

You need to prove a cable's insulation is sound, after installation, after damage, or because a breaker or RCD keeps tripping. A megger test answers that, provided the cable is isolated properly and you test every combination of conductors.

As an Amazon Associate, Akermin earns from qualifying purchases. Product links on this page are affiliate links.

Isolate the circuit, lock it off, prove it dead, and disconnect the cable at both ends so no equipment is connected. Then use an insulation resistance tester at the correct DC voltage, typically 500 V for ordinary low-voltage cables up to 500 V, and test each conductor to earth and each conductor to every other conductor, recording the megohm reading after it settles. Under common wiring rules for low-voltage installations the minimum acceptable reading is 1 megohm, but a healthy cable usually reads far higher, often hundreds of megohms or more. Discharge the cable after every test.

What the megger actually measures

An insulation resistance tester, often called a megger after one well-known brand, applies a high DC voltage between two conductors and measures the tiny current that leaks through the insulation. It divides voltage by current and shows the result in megohms or gigohms. Good insulation lets almost nothing through, so the reading is very high. Moisture, contamination, heat damage, nicks and cuts all let more current through and pull the reading down.

This is a different test from continuity. A continuity tester or multimeter checks that a conductor connects end to end with low resistance. An insulation tester checks that it does not connect to anything it should not. The distinction is laid out in insulation tester vs continuity test. You normally need both when proving a cable.

A multimeter cannot do this test. Its resistance range uses a few volts, which does not stress the insulation enough to reveal weaknesses that show up at working voltage.

Before testing: isolation and safety

Insulation testing is done on dead circuits only, and the test itself produces hazardous voltage.

  1. Isolate and lock off the supply at the protective device, and fit a lock and warning label so it cannot be switched on while you work.
  2. Prove dead with an approved voltage tester, checked on a known live source or proving unit before and after.
  3. Disconnect both ends of the cable from all equipment. Electronic devices, dimmers, RCD electronics, surge protectors, LED drivers, variable speed drives and anything with a control board can be damaged by the test voltage and will also give false low readings.
  4. Warn others. Make sure nobody is at the far end touching the conductors. Tape or cover far-end cores so they cannot be touched during the test.
  5. Use a tester rated for the job. Check its leads and CAT rating, and confirm it has a live circuit warning.

If you are not trained and competent to isolate circuits, this test belongs to a qualified electrician.

Choosing the test voltage and the pass value

Circuit nominal voltage Typical DC test voltage Commonly used minimum
Extra-low voltage (SELV, PELV) 250 V 0.5 megohm
Up to 500 V, including 230 V and 400 V systems 500 V 1 megohm
Above 500 V up to 1000 V 1000 V 1 megohm
Medium and high voltage cables Often 2.5 kV, 5 kV or higher Set by the cable maker and the applicable standard

These figures follow common low-voltage wiring rules such as those derived from IEC 60364; your local code and the cable manufacturer have the final word. Treat the minimum as a floor, not a target. A new cable reading just over 1 megohm is suspect, and many electricians investigate anything under about 2 megohms. What matters most is comparison: identical cores in the same cable should read similar values, and a cable should not fall sharply between tests. Multi-function installation testers such as the Kyoritsu KEW 6010B multi-function tester or the digital insulation tester with RCD and loop testing combine insulation testing with loop and RCD tests; confirm in the manual which insulation test voltages your unit provides before you start.

The test, conductor by conductor

  1. Check the tester. Short the leads together on the insulation range: it should read zero or close to it. Separate them: it should read above its maximum range.
  2. Select the test voltage from the table above.
  3. Test each conductor to earth. Connect one lead to the earth conductor or cable armour and the other to each core in turn: line to earth, neutral to earth, and each phase on three-phase cables.
  4. Test between conductors. Line to neutral, and on multi-core cables every core to every other core. A quick method is to link all cores except one, test that one against the linked group, then repeat for each core.
  5. Hold the test until the reading settles. On long cables the reading rises for some seconds as the cable charges. Record the value after it stops climbing, or at a fixed time such as one minute for consistency.
  6. Discharge. Most testers discharge the cable automatically when you release the button; wait for the voltage indicator to drop before touching conductors. Long cables store a dangerous charge.
  7. Record everything: conductors tested, test voltage, reading, temperature and date.

Interpreting what you get

Result Likely meaning Action
Very high, above the tester’s range Healthy insulation Record and reconnect
Tens to hundreds of megohms Usually acceptable; older cables read lower Compare cores and past results
Just above the minimum Damp, aged or contaminated insulation Investigate before energising
Below the minimum Insulation fault Do not energise; locate the fault
Near zero Direct short or connected equipment Recheck disconnections; split the circuit
One core much lower than the others Local damage on that core Inspect terminations and the route

Insulation resistance falls as temperature rises, roughly halving for each ten degrees Celsius or so on many insulation types, so compare readings taken at similar temperatures. On larger cables and motor feeders, a polarisation index test compares the ten-minute reading with the one-minute reading; a ratio that stays close to 1 suggests damp or contaminated insulation.

For finding the location of a low reading, split the circuit at junction boxes and test each section. Terminations, glands and junction boxes where water has got in are the usual culprits. Low-resistance checks on joints are a separate job for a milliohm meter.

Reconnecting and when to call for help

After passing, reconnect all equipment, check terminations are tight, and carry out the remaining required tests, such as continuity of protective conductors, polarity and loop impedance, before energising. If a cable fails, especially an underground or armoured cable, a buried run, or a medium-voltage cable, bring in a qualified electrician or cable test specialist; locating faults on long runs uses dedicated equipment. A comparison of instruments is in our guide to insulation resistance testers.

Test it twice, a day apart if it is borderline

If your cable reads above the minimum but well below the other cores or below about 2 megohms, leave it disconnected, dry out any terminations or junction boxes that could hold moisture, and retest the next day at the same voltage. A reading that rises after drying points to damp ends; one that stays low points to damage in the run, which needs locating before the circuit goes back into service.

Frequently Asked Questions

What is a good megger reading for a cable?

For low-voltage cables tested at 500 V, common wiring rules set a minimum of 1 megohm, but healthy cables usually read hundreds of megohms or more. A reading close to the minimum calls for investigation even though it technically passes.

Can I megger test a cable with equipment connected?

You should not. Electronic equipment can be damaged by the test voltage and will drag the reading down, so disconnect the cable at both ends or remove all connected loads first.

Why does the megger reading keep rising during the test?

The cable behaves like a capacitor and the insulation material polarises, so the measured current falls over the first seconds or minutes. Wait until it settles, or read at a fixed time for comparison.

Is a megger test the same as a continuity test?

No. Continuity checks that a conductor connects with low resistance, while insulation testing checks that conductors are not leaking to each other or to earth at high voltage.

Do I need to discharge a cable after insulation testing?

Yes. A long cable can hold a dangerous charge after the test, so let the tester's discharge function finish and confirm the voltage has dropped before touching the conductors.