Lock out the unit, prove it dead, remove the three power leads from the compressor terminals, and test each terminal to a clean, bare spot on the compressor shell or copper line at 500 V DC for about a minute. A healthy hermetic compressor normally reads in the hundreds of megohms or more; low single-digit megohms is suspect, and a reading near zero or below about 1 MΩ means a grounded winding and the compressor should not be restarted. Never test a compressor that is under deep vacuum, and if the reading is low on a cold unit, warm it with the crankcase heater and retest before condemning it.
What can drag a compressor reading down
A hermetic or semi-hermetic compressor has its motor windings sealed inside the shell, bathed in refrigerant and oil. The insulation test measures leakage from the windings to the shell, which is earthed. That leakage path includes the winding insulation, the internal leads, the terminal block or fusite, and anything that the refrigerant and oil carry.
| Cause | How to spot it | Next step |
|---|---|---|
| Liquid refrigerant and oil in the shell | Low reading on a cold compressor after an off cycle; improves after warming | Energize the crankcase heater for several hours and retest |
| Moisture or acid in the system | Low reading on all terminals, dark or acidic oil, history of a leak or burnout | Acid test, filter drier change, system cleanup by a certified technician |
| Dirty or wet terminal block | Visible oil, dust or corrosion on the terminals; reading improves after cleaning | Clean and dry terminals and retest |
| Grounded winding | Very low or zero on one or more terminals, stays low when warm and clean | Compressor replacement |
| Leads still connected | Low reading that includes contactor, crankcase heater or monitoring module | Remove the leads from the compressor terminals |
Refrigerant and oil inside the shell conduct far better than dry gas. That is why the same compressor can read a few megohms cold and hundreds of megohms after the crankcase heater has driven the liquid out.
Before you connect the tester
- Lock out and prove dead. Open the disconnect, apply a lock and tag, and test with a rated voltage tester phase to phase and phase to ground at the compressor contactor load side. Many units also have separate control power; isolate that too.
- Do not test under vacuum. If the system has been evacuated, do not insulation test or energize the compressor. Insulation breaks down at much lower voltage in a deep vacuum, and the test can damage the motor windings. Break the vacuum with refrigerant or dry nitrogen first.
- Respect the terminals. Compressor terminal pins can blow out under system pressure, especially if damaged or overheated. Keep your face and hands out of line with the terminals, and do not energize the compressor with the terminal cover off.
- Leave refrigerant work to certified people. Recovering, evacuating or charging refrigerant requires the appropriate certification in most countries.
- Identify extra devices. Electronic protection modules, crankcase heaters and phase monitors are separate circuits. Remove their leads from the compressor terminals or test them separately.
Testing the compressor, step by step
- Remove the terminal cover and photograph the wiring so the leads go back on the right terminals, usually marked T1, T2 and T3.
- Remove the three power leads from the terminals. Keep them apart so the tester does not see the wiring and contactor.
- Clean the terminal block if it is oily or dirty, and let it dry.
- Find a clean, bare earth point: an unpainted bolt on the shell, or scrape a small area on the suction or discharge copper line. Paint and corrosion will add resistance and spoil the reading.
- Select 500 V DC on the insulation tester. That is the usual test voltage for 208 to 600 V compressors; follow the compressor maker’s instruction if it specifies otherwise.
- Clip the earth lead to the shell point and the line lead to T1. Press and hold for one minute and record the value. Repeat for T2 and T3.
- Let the tester discharge before moving the leads.
- Check winding resistance next. With a multimeter or a milliohm meter, measure T1 to T2, T2 to T3 and T1 to T3. On a healthy three-phase motor the three values are equal within a few percent. A Extech 380560 milliohm meter reads these low values more precisely than a standard multimeter, which matters on larger compressors where windings are well under one ohm. Background is in milliohm meters for low resistance testing.
- Record the readings, the shell temperature and whether the crankcase heater was on.
Reading the numbers
Compressor makers publish their own minimums, so check the service literature. As general field guidance:
| Reading, terminal to shell, 500 V DC | Interpretation |
|---|---|
| Over-range or hundreds of megohms and higher | Healthy insulation |
| Tens of megohms | Acceptable, but compare with previous tests and watch the trend |
| A few megohms or less, cold | Warm with crankcase heater and retest; check oil and system moisture |
| Below about 1 MΩ after warming | Insulation failing; do not restart |
| Near zero | Grounded winding; compressor needs replacing |
A trend matters more than one reading. A compressor that falls from 500 MΩ to 20 MΩ over a season is breaking down, often from moisture or acid, even if 20 MΩ still passes. A low reading combined with dark, acidic oil points to a burnout, which needs a full system cleanup, not just a new compressor.
Unequal winding resistance with good insulation points to a shorted turn or open winding instead. Insulation and continuity tests answer different questions, as explained in insulation tester versus continuity test.
When to stop and call for help
A grounded compressor can put voltage on the shell, refrigerant lines and cabinet if protection does not clear the fault, and restarting a failing compressor can blow out a terminal and release hot refrigerant and oil. Do not restart a compressor that reads below the maker’s minimum after warming.
Bring in a licensed HVAC or refrigeration technician for compressor replacement, refrigerant recovery, acid cleanup and any work you are not certified for. If the supply side, such as the breaker, contactor or feeder, is suspect, that is a job for a qualified electrician. For choosing a tester for this kind of work, see insulation resistance testers.
Record the results the same way every time: terminal, reading at one minute, test voltage, shell temperature, ambient temperature and whether the unit had been running. A compressor that has just stopped after a long run is hot and its reading will be lower than the same compressor on a cool morning, so like-for-like records make trends meaningful.
Warm it before you condemn it
If your first reading on a cold compressor is low, reconnect power to the crankcase heater only, give it several hours, then lock out again and retest each terminal at 500 V DC. A reading that climbs well into the megohms tells you the problem was refrigerant in the shell; one that stays low confirms a winding fault.
Frequently Asked Questions
Can I megger a compressor without removing the wires?
You can screen it from the contactor load side, but the reading includes the wiring and any connected devices. To judge the compressor itself, remove the leads at its terminals.
Why is it dangerous to megger a compressor in a vacuum?
Insulation holds off much less voltage in a deep vacuum, so the test voltage can arc inside the shell and damage the windings. Always break the vacuum before testing or starting the compressor.
What test voltage should I use on a 460 V compressor?
500 V DC is the common choice. Use the compressor manufacturer's specified value if it gives one.
My compressor reads fine on insulation but trips the breaker. Why?
The fault may be a shorted turn, a locked rotor, a failed contactor, unbalanced supply voltage or a mechanical problem. Check winding resistance balance, supply voltage on all three phases and running current.
Does a low reading always mean the compressor is bad?
No. Refrigerant and oil in a cold shell, or a dirty terminal block, can give a low reading on a good compressor. Warm, clean and retest before deciding.