Isolate and prove the motor dead, disconnect the supply leads at the terminal box, and remove or disconnect the start or run capacitor so it is not charged by the test. Then join the winding leads together, or test each lead in turn, and measure from the windings to a clean bare spot on the motor frame at 500 V DC for one minute. Healthy motors usually read hundreds of megohms or higher; a reading in the low megohms points to moisture or contamination, and anything close to zero means a winding is grounded and the motor should not be run.
What is inside a single phase motor that affects the test
A single-phase induction motor has a main or run winding and an auxiliary or start winding, with a capacitor, a centrifugal switch or an electronic relay to create the rotating field at start-up. Some motors also have a thermal protector inside the windings. Each part affects how you test.
| Component | Effect on the insulation test | What to do |
|---|---|---|
| Start or run capacitor | Charges to the test voltage and stores a shock; a leaky capacitor can lower the reading | Disconnect one capacitor terminal and discharge it |
| Centrifugal switch | Closed at rest, so the start winding is connected; no harm to the test | Leave as is; it ensures both windings are tested |
| Electronic start relay or speed control | Can be damaged by 500 V DC | Disconnect from the windings before testing |
| Thermal protector | Usually in series with the windings; if open, part of a winding may not be tested | Let the motor cool; check continuity through the protector |
| Internal links or dual-voltage connections | Determine which leads connect to which winding | Check the connection diagram on the plate or cover |
The windings are connected together inside through copper, so for an insulation test you treat all of them as one conductor and measure from that conductor to the frame.
Isolation and set-up
- Lock out the supply at the breaker, switch or plug. If the motor is plug-connected, unplug it and keep the plug in your control.
- Prove dead at the motor terminals with a rated voltage tester, checked on a known live source before and after.
- Open the terminal box and note or photograph the connections.
- Disconnect the supply leads from the motor terminals, so the test covers the motor only and not the cord, switch or controller.
- Disconnect the capacitor. Lift one lead, then discharge the capacitor safely, for example through a resistor rated for the job. Never short it with a screwdriver; it can damage the capacitor and weld the tip.
- Disconnect electronics such as speed controllers or electronic starting relays.
- Find a bare frame point, such as the earth terminal in the box or a scraped area on the frame. Paint gives a false high resistance between your clip and the frame.
Running the test and the readings that matter
- Select 500 V DC on the insulation tester. That suits motors rated 120 V, 230 V and 240 V, and matches the IEEE 43 guidance for machines below 1,000 V. Use 250 V only if the manufacturer specifies it.
- Do an open-lead test first: separated leads should read over-range.
- Clip the earth lead to the frame and the line lead to the winding leads, either twisted together or one at a time. Testing each lead separately tells you more if the reading is low.
- Press and hold for one minute. Watch the reading; on dry, clean insulation it should climb steadily as the absorption current fades.
- Record the one-minute value and the motor temperature.
- Release and let the tester discharge the windings before touching anything.
Interpreting the number:
- Hundreds of megohms or over-range: insulation is healthy.
- Tens of megohms: usually acceptable; watch the trend.
- Low megohms: IEEE 43 gives a commonly cited minimum of 5 MΩ for random-wound machines below 1 kV, corrected to 40 degrees C. Below that, investigate for moisture, dirt or damage.
- Below about 1 MΩ or near zero: a grounded winding. On an RCD- or GFCI-protected circuit this is the classic cause of tripping at start.
Remember that insulation resistance roughly halves for every 10 degrees C rise, so a motor tested hot reads lower than the same motor cold.
If one lead reads much lower than the others, the fault is on that winding or its lead. If all leads are equally low, moisture or contamination across the whole winding is more likely, which is common on pump motors and fans exposed to weather.
Winding resistance: the check that goes with it
An insulation test proves the windings are separated from the frame; it does not prove the windings themselves are intact. For that, use the low-resistance range of a multimeter, or a milliohm meter for small values, with the capacitor disconnected.
On a capacitor motor with three leads, usually common (C), start (S) and run (R), measure C to R, C to S and S to R. The run winding normally has the lowest resistance, the start winding is higher, and S to R should equal the sum of the other two. An open reading on any pair means a broken winding or an open thermal protector. A reading far lower than expected suggests shorted turns.
The two tests answer different questions, and confusing them is a common mistake, covered in insulation tester versus continuity test. For small winding values on larger motors, see milliohm meters for low resistance testing.
A multifunction tester such as the Kyoritsu KEW 6010B handles both the insulation and continuity checks in one instrument, while the Srliya digital insulation tester pairs insulation testing with loop and RCD functions. A scope-meter like the FNIRSI 2C53P has a normal ohms range for windings but no insulation test voltage, so it cannot replace a megger here.
If the motor fails, and when to call a professional
A damp motor, especially on a pump or outdoor fan, can often be recovered. Dry it in a warm, ventilated place or with gentle heat, well below the insulation class temperature, and retest. A reading that climbs steadily as it dries confirms moisture. If it stays low once dry, the insulation is broken down and the motor needs rewinding or replacing; for small motors, replacement is usually more practical.
Do not run a motor with a grounded winding. It can trip protection, but on a circuit without RCD or GFCI protection and with a poor earth, the frame can become live. Call a qualified electrician if the motor is hard-wired and you are not trained in safe isolation, and use a motor repair shop for rewinds. For choosing a suitable tester, see insulation resistance testers.
Test leads one by one
On your next test, disconnect the capacitor, then test each winding lead to the frame separately at 500 V DC and write down all three values with the motor temperature. One low lead points you straight to the faulty winding, while three equally low readings tell you to dry the motor and test again.
Frequently Asked Questions
Do I need to remove the capacitor to megger a motor?
Disconnect at least one capacitor terminal. Otherwise the capacitor charges to the test voltage, stores a shock and can lower or confuse the reading if it is leaky.
Can I megger a motor while it is still wired to the switch?
You can screen the whole circuit, but the result includes the cable and switch. Disconnect at the motor terminals to judge the motor on its own.
Why does my motor trip the GFCI but read fine on a multimeter?
A multimeter uses only a few volts and cannot detect leakage that appears at mains voltage. An insulation test at 500 V DC can reveal the weak insulation the multimeter misses.
What reading should a new single phase motor give?
A new, dry motor usually reads hundreds of megohms or over-range at 500 V DC. A much lower reading on a new motor suggests moisture from storage or a manufacturing fault.