A megger reading is the insulation resistance between conductors, or between a conductor and earth, measured at a set DC test voltage, usually shown in megohms (MΩ) or gigaohms (GΩ). Higher is better: healthy new cable and equipment often read hundreds of megohms or over the meter’s range, while low single-digit megohm readings point to moisture, contamination or damage. Compare the number with the minimum for that equipment and test voltage, for example the 1 MΩ minimum many wiring rules set for low voltage circuits at 500 V, then check how it compares with previous tests and, for motors and large cables, the polarization index over ten minutes.
What the instrument is measuring
An insulation resistance tester applies a steady DC voltage, commonly 250 V, 500 V or 1,000 V, and higher for medium voltage equipment, across insulation and measures the tiny current that leaks through or across it. Resistance is voltage divided by that current, so a leakage of 1 microamp at 500 V means 500 MΩ.
The current has three parts. A capacitive charging current that falls away within seconds, an absorption current that falls slowly over minutes as the insulation material polarises, and a leakage current that stays steady and represents real conduction through or over the insulation. Because the first two decay, the resistance reading climbs during the test. That is normal, and it is the basis for the time-ratio tests below.
A continuity test is a very different measurement: a low-voltage, low-resistance check that a conductor is unbroken, read in ohms. The two are often done with the same multifunction tester, which is why results sheets list both. The difference is explained in insulation testers versus continuity tests.
Reading the display and the results sheet
- Test voltage. Always note it; a result means nothing without it. A reading at 250 V is not directly comparable with one at 1,000 V.
- Units. MΩ is a million ohms; GΩ is a thousand megohms. A reading of 2.4 GΩ is 2,400 MΩ.
- Greater-than readings. A display of something like >299 MΩ or >999 MΩ means the insulation is better than the instrument can measure on that range. That is a pass for most purposes; record it as written.
- Test pairs. Results are listed per pair, such as line to neutral, line to earth and neutral to earth, or phase to phase and phase to earth on three-phase equipment. Check every pair; one low pair is enough to fail.
- Time. Spot readings are usually taken at one minute. Longer tests record values at 30 seconds, one minute and ten minutes.
Multifunction testers such as the KYORITSU KEW 6010B combine continuity, insulation, loop and RCD tests and store results, which makes comparing with earlier tests much easier.
Is the number good enough?
Minimum values depend on the equipment, the test voltage and the rules you work under, so always check the standard or the manufacturer’s data. Common reference points:
| Equipment | Typical test voltage | Common minimum | What healthy usually looks like |
|---|---|---|---|
| Building wiring, low voltage circuits | 500 V | 1 MΩ under many wiring rules, including BS 7671 | Tens to hundreds of MΩ, often over range |
| Extra-low voltage circuits | 250 V | 0.5 MΩ under BS 7671 | Well above the minimum |
| Low voltage motors | 500 V or 1,000 V | Set by maker or IEEE 43 guidance | Hundreds of MΩ when clean and dry |
| PV strings and arrays | Per IEC 62446 guidance, often 500 V or 1,000 V | Set by the standard and system voltage | Varies with array size and moisture |
Treat the minimum as the line below which equipment must not be energised, not as a target. A building circuit reading 2 MΩ passes the 1 MΩ minimum but is far below a typical new installation, and suggests damp, damage or a connected load. Investigate it.
Long cable runs and many parallel circuits read lower simply because there is more insulation in parallel. Ten circuits each at 100 MΩ, tested together, read about 10 MΩ. Split them and test individually before deciding one is faulty. Solar installations bring their own considerations, covered in solar insulation resistance testers.
Time ratios, temperature and trends
Polarization index (PI) is the ten-minute reading divided by the one-minute reading. Dielectric absorption ratio (DAR) is the one-minute reading divided by the 30-second reading. Clean, dry insulation keeps rising, so the ratios are well above 1. Moist or contaminated insulation lets leakage dominate, so the reading flattens early and the ratio falls toward 1.
- PI below 1: poor, investigate before energising.
- PI about 1 to 2: questionable, often damp or dirty.
- PI about 2 to 4: generally good.
- Above 4: very good for many insulation types.
Example: a motor reads 400 MΩ at one minute and 1,600 MΩ at ten minutes, so PI is 4.0, a healthy winding. Another reads 40 MΩ and 44 MΩ, a PI of 1.1: the absolute value might pass a minimum, but the flat curve suggests moisture, and drying the winding before service is the safer call. Modern insulation systems with very high resistance can show unusual PI values, so read them with the maker’s guidance.
Temperature matters. Insulation resistance falls as temperature rises; a common rule of thumb is that it roughly halves for every 10 °C increase. Record winding or ambient temperature with each test, and correct to a reference temperature before comparing results.
Trend is often the most useful information. A motor that read 800 MΩ last year and reads 80 MΩ now, at the same temperature and voltage, is deteriorating even though both readings pass.
Safety and testing errors
Insulation testers generate high voltage. Test only isolated, dead circuits, proved dead with an approved voltage tester and locked off. Disconnect or link out electronic devices such as dimmers, surge protectors, drivers, smart switches and VFD outputs, which can be damaged or can give false low readings. Capacitive loads, long cables and motor windings store charge during the test; let the instrument discharge them, or discharge them safely, before touching conductors. Work on building wiring and switchgear should be done by a qualified electrician.
Common errors that produce misleading results include testing with loads connected, damp or dirty test leads, surface contamination on terminals, and comparing tests at different voltages. Low resistance measurements, such as bonding conductors and joints, use a different instrument altogether; see milliohm meters for low resistance testing. For choosing an insulation tester, the guide to insulation resistance testers compares voltages and ranges.
Compare with the last test
Find the previous test sheet for the same equipment, check that the test voltage and temperature were similar, and set the readings side by side. If any pair has dropped by a large factor or the polarization index has fallen toward 1, schedule cleaning, drying or a qualified inspection before the next energisation.
Frequently Asked Questions
What does a reading of infinity or OL mean on a megger?
It means resistance is above the instrument's top range at that voltage, so leakage is too small to measure. For most equipment that is a very good result.
Why does the megger reading keep rising during the test?
Capacitive and absorption currents decay over time, leaving only true leakage. Rising resistance is normal and indicates healthy, dry insulation.
Can I megger test a circuit with LED lights connected?
Disconnect or isolate electronic loads first. They can be damaged by the test voltage and can make the insulation look faulty when it is not.
What test voltage should I use?
Follow the wiring rules or the equipment maker. Many low voltage circuits are tested at 500 V, extra-low voltage at 250 V, and motors and larger cables at 500 V or 1,000 V.
Is 1 MΩ a good insulation reading?
It may meet the minimum for low voltage circuits under some wiring rules, but healthy installations usually read far higher. A reading near the minimum deserves investigation.