How to Megger Test With a Fluke 1587 FC

You have a Fluke 1587 FC insulation multimeter and need to run an insulation resistance test on a motor, cable or circuit. The meter does most of the work, but setting it up and isolating the circuit correctly is what makes the number valid.

Isolate the circuit and prove it dead first, because the 1587 FC will refuse to test, or give a meaningless result, if voltage is present. Plug the leads into the insulation test input and COM sockets, turn the rotary dial to the insulation position, and select a test voltage suited to the equipment, commonly 500 V for low-voltage wiring and 1000 V for motors and circuits rated up to around 600 V. Connect one lead to the conductor and the other to ground or the other conductor, then press and hold the TEST button on the meter or the remote probe until the reading stabilises. Release the button, let the meter discharge the circuit, and record the megohm reading with the test voltage and temperature.

What the 1587 FC does when you press TEST

The 1587 FC is a combined digital multimeter and insulation resistance tester. In normal multimeter positions it measures voltage, resistance and other quantities using its own battery-powered low-energy circuits. In the insulation position, it generates a regulated DC test voltage, applies it between the two test leads, and measures the very small leakage current that flows through the insulation. Dividing the test voltage by the leakage current gives insulation resistance, displayed in megohms or gigohms.

Because the voltage is high and the measured current is tiny, two things matter. The conductor under test must be completely de-energised and disconnected from anything that should not see the test voltage, and the reading takes time to settle as the cable or winding capacitance charges. The FC in the name refers to its wireless connectivity; it can send readings to a phone app for logging and, depending on the app features, timed tests such as polarisation index. The insulation test itself works the same with or without the app.

The concept is explained further in insulation tester vs continuity test, which is worth reading if you are new to megohm testing.

Choosing the test voltage

The 1587 family offers a range of selectable insulation test voltages. Pick the one that suits the voltage rating of the equipment, not the highest one available. Use the manufacturer’s recommendation and your local wiring standard where they specify a value.

Equipment Common test voltage Notes
Extra-low voltage or electronics-adjacent circuits 50 V to 250 V Disconnect or bypass electronics entirely where possible
Household and commercial wiring, up to about 500 V 500 V A typical value for low-voltage installation testing in many regions
Motors and circuits rated up to about 600 V or 690 V 1000 V Common for motor windings and feeders in that class
Higher voltage equipment Beyond this meter’s range Use a dedicated medium-voltage insulation tester

The values in this table are common practice rather than universal rules. If a motor nameplate, cable standard or site procedure gives a test voltage, follow it. Applying a test voltage well above the equipment rating stresses the insulation and can damage connected devices.

Step-by-step insulation test with the 1587 FC

  1. Isolate and lock out. Switch off, lock and tag the supply. Prove dead with a properly rated voltage tester, proving it before and after.
  2. Disconnect what should not be tested. Remove or isolate drives, electronic controls, surge protectors, lamps, capacitors and the neutral to earth link where your procedure requires. Anything electronic left connected can be damaged or will drag the reading down.
  3. Insert the leads. Black into COM, red into the insulation input socket. On the 1587 family the insulation test shares an input with volts; check the sockets marked on your meter and in the manual.
  4. Turn the dial to the insulation position. Use the selection button to step through the available test voltages until the one you want is displayed.
  5. Connect to the circuit. For phase to earth: red on the conductor (or on all phase conductors shorted together), black on earth. For phase to phase: red on one conductor, black on another.
  6. Press and hold TEST. Use the button on the meter or the remote test probe. The display shows the test voltage being applied and the insulation reading. Hold until the reading is stable, typically several seconds for short cables and longer for long feeders or motors.
  7. Release and wait for discharge. The meter discharges the circuit through its internal resistance. Do not disconnect the leads until the display shows the voltage has fallen to a safe level.
  8. Record. Note test voltage, reading, conductor pair and temperature, or let the app log them.

Reading the result and checking the meter

Insulation readings are judged against a minimum, against previous tests and against similar equipment:

  • Very high reading or display over range. Healthy insulation on short cables often reads beyond the meter’s top range. That is a pass, not an error.
  • Reading that climbs during the test. Normal; capacitance charging and dielectric absorption raise it. A slowly rising reading over a minute is a sign of good dry insulation.
  • Low or falling reading. Moisture, contamination, damaged insulation or something still connected. Recheck what is attached before concluding the insulation has failed.
  • Near zero. A direct fault to earth, a connected neutral to earth link, or a device still in circuit.

Minimum acceptable values come from your wiring regulations, the manufacturer or a testing standard, and they depend on circuit type and test voltage. For motors, comparing the 1-minute and 10-minute readings as a polarisation index helps separate moisture from simple surface leakage.

Before trusting the meter, check it. With the leads open, an insulation test should read over range; with the leads shorted, it should read near zero and the meter should behave as the manual describes. Insulation testers in general are covered in insulation resistance testers, and the solar variants in solar insulation resistance testers.

Errors, refusals and safety limits

  • The meter will not start the test. It has detected voltage on the circuit, typically above a few tens of volts. That is a safety lockout. Find and remove the source; do not try to work around it.
  • Battery low warning. Insulation testing draws much more battery than normal multimeter use. Replace batteries before a big job; a weak battery can prevent the meter reaching the test voltage.
  • Readings jump around. Long feeders are capacitive and noisy. Hold the test longer, keep leads still and away from live conductors, and use the guard technique where appropriate.
  • Shock after the test. A long cable or motor stores charge. Always let the meter discharge it, and ground it before touching.

Insulation testing applies hundreds to a thousand volts. Warn others, barrier the far end of cables, and never test while anyone can touch the conductor. Work on fixed installations is regulated in many places; if you are not qualified for it, use a licensed electrician.

Do a dry run on a known cable

Before testing the real job, take a short spare length of cable, test core to core at 500 V and confirm the 1587 FC reads over range, then short the far end and confirm it reads near zero. Once you have seen both extremes, you will recognise a genuine fault reading on the circuit that matters.

Frequently Asked Questions

Why does my Fluke 1587 FC not run an insulation test?

Most often it detects voltage on the circuit and blocks the test as a safety measure. Other causes are a low battery, the dial not in the insulation position or the lead in the wrong socket.

Can the 1587 FC do a polarisation index test?

The 1587 FC is designed to support timed insulation tests such as polarisation index and dielectric absorption ratio, particularly when used with its companion app. Check the manual for the exact procedure on your firmware.

Is the remote probe necessary?

No, but it lets you start and stop the test from the probe without reaching for the meter, which is safer and easier when your hands are on the leads.

What reading means a cable has passed?

Pass values depend on your wiring regulations and the test voltage used. Many low-voltage standards set a minimum in the low megohms, and healthy new cable often reads far higher, sometimes over the meter's range.

Do I need to disconnect electronics before an insulation test?

Yes. Drives, dimmers, smart switches, surge devices and anything with semiconductors can be damaged by the test voltage or will give a misleadingly low reading. Disconnect them or test only the cable.