How to Megger Test a Dry Type Transformer

You need an insulation resistance reading on a dry-type transformer, for commissioning, after a flood or overheating event, or as part of maintenance. The test is simple once the transformer is isolated properly, but the setup decides whether the numbers mean anything.

As an Amazon Associate, Akermin earns from qualifying purchases. Product links on this page are affiliate links.

De-energise and lock out the transformer, prove it dead, and disconnect everything attached to the windings: line and load cables, surge arresters, the neutral to ground bond and any control or fan wiring. Short all the high-voltage terminals together and all the low-voltage terminals together, then measure insulation resistance three ways: high side to low side, high side to ground with low side grounded, and low side to ground with high side grounded. Use a DC test voltage suited to each winding’s rating, hold it for one minute or longer for a polarisation index, record the winding temperature, and discharge each winding to ground afterwards. Compare results with the manufacturer’s data or industry acceptance tables and with past readings from the same unit.

What the insulation test tells you about a dry-type unit

An insulation resistance tester applies a high DC voltage between a winding and something it is meant to be insulated from, then measures the tiny leakage current that flows. The result, in megohms or gigohms, reflects the condition of the insulation system: the varnish or resin on the conductors, the barriers between windings, the core insulation and the surfaces of the coils.

Dry-type transformers are more sensitive to surface condition than oil-filled ones. Their coils are exposed to room air, so dust, moisture and contamination on the surfaces show up as lower readings. A reading that is low only on a humid day, then recovers after the unit is dried or cleaned, is a surface problem. A reading that is low and keeps falling over the minutes of the test points to moisture or deterioration in the insulation itself.

Insulation resistance is not the same as a continuity or winding resistance check. The difference is covered in insulation tester vs continuity test; a winding resistance test needs a low-resistance meter such as those in milliohm meters for low resistance testing.

Isolating and preparing the transformer

  1. Plan the outage and permits. This test is done by qualified electrical workers under the site’s safety program. The transformer is de-energised from every source, including back-feeds from generators or other transformers.
  2. Lock out, tag out and prove dead. Verify absence of voltage on both windings with a properly rated tester, then apply temporary protective grounds as your procedure requires. Grounds on the winding under test have to be lifted for the measurement itself, so follow your procedure for removing and restoring them safely.
  3. Disconnect external connections. Lift the line and load cables, or at minimum isolate them at both ends, because cable insulation in parallel with the winding lowers the reading. Disconnect surge arresters, capacitors and any control, fan or temperature-monitor wiring connected to the windings.
  4. Remove the neutral to ground bond on wye-connected secondaries, often an X0 to frame link. Otherwise the low-voltage winding is grounded and you are measuring the bonding jumper.
  5. Short each winding. Use flexible jumpers to connect all high-voltage terminals together (H1, H2, H3) and all low-voltage terminals together (X1, X2, X3, plus X0 if present). This keeps the test voltage across the insulation, not across the winding’s own turns.
  6. Clean and dry if needed. Note the condition of the coils and record ambient temperature and humidity.

The three measurements and suggested test voltages

Test Line lead to Earth lead to Guard or grounding
High side to low side Shorted HV terminals Shorted LV terminals Frame and core grounded; use the guard terminal to remove surface leakage paths if needed
High side to ground Shorted HV terminals Frame or enclosure ground Shorted LV winding connected to ground
Low side to ground Shorted LV terminals Frame or enclosure ground Shorted HV winding connected to ground

Choose the DC test voltage from the winding’s voltage class. A common approach is around 1000 V DC for windings rated up to about 600 V, and higher test voltages, typically 2500 V or 5000 V DC, for medium-voltage windings. Do not exceed the manufacturer’s recommended value; on low-voltage windings, testing well above the rating stresses insulation needlessly. Industry testing standards such as NETA’s acceptance and maintenance specifications list test voltages and minimum values by voltage class; use those, or the manufacturer’s data, as the authority for your equipment.

An installation tester such as the KYORITSU KEW 6010B can cover the low-voltage winding if its insulation range reaches the test voltage you need. Medium-voltage windings need a dedicated higher-voltage tester; see insulation resistance testers.

Running each test and recording the numbers

  1. Connect the tester with it switched off. Line lead to the winding under test, earth lead to the reference, guard lead if you are using it.
  2. Apply the test voltage and start timing. Watch the reading rise as the winding’s capacitance charges and absorption currents decay.
  3. Record at 30 seconds and 1 minute for a dielectric absorption ratio, and at 1 and 10 minutes for a polarisation index (PI). The PI is the 10-minute reading divided by the 1-minute reading.
  4. Release and discharge. Most testers discharge automatically; wait until the tester shows the voltage has bled off, then ground the winding with a grounding stick for at least as long as the test ran. A transformer winding stores charge and can deliver a shock long after the test.
  5. Record winding temperature. Insulation resistance drops sharply as temperature rises, roughly halving for every 10 degrees C, so readings must be corrected to a base temperature, often 20 degrees C, before comparison.
  6. Repeat for the other two configurations.

A worked correction: a reading of 2,000 megohms at 40 degrees C corrected to 20 degrees C is about 2,000 x 2 x 2, or 8,000 megohms, using the halving rule. Use the correction tables in your standard for precise factors.

Interpreting results and when to stop

  • Compare against references. Manufacturer data and published acceptance tables give minimum values by voltage class. Trend against earlier tests on the same unit; a large drop is more meaningful than any single absolute number.
  • Look at PI or DAR. A reading that rises steadily during the test shows healthy insulation. A flat or falling reading suggests moisture or contamination. Dry-type insulation can show lower PI values than oil-filled units, so compare like with like.
  • Low on one test only. HV to ground low while HV to LV is fine points to the HV winding’s insulation to the core or frame, or a dirty HV bushing or support.
  • Surface versus bulk. If using the guard terminal raises the reading a lot, leakage is across surfaces; cleaning and drying may fix it.

Do not re-energise a transformer with readings below acceptance values or that fell substantially since the last test. Common remedies are cleaning, controlled drying with heaters or short-circuit current, and retesting. Persistent low readings, signs of tracking, burnt insulation or a failed PI warrant the manufacturer or a specialist testing firm. Remove all jumpers and restore the neutral to ground bond before energising.

Write the test sheet before you start

Before the outage, make a sheet with the three test configurations, the test voltage for each winding, columns for 30 second, 1 minute and 10 minute readings, and a box for winding temperature and humidity. Fill it in on site, correct to your base temperature, and file it with the transformer’s records so the next test has a trend to compare against.

Frequently Asked Questions

What voltage should I use to megger a 480 V dry-type transformer?

A test voltage around 1000 V DC is commonly used for windings rated up to about 600 V. Check the manufacturer's instructions and your site's testing standard, and do not exceed the recommended value.

Do I need to disconnect the neutral before testing?

Yes, on a wye secondary the neutral to ground bond must be removed for the low side to ground test, or the reading will be essentially zero. Restore the bond before re-energising.

Why short the winding terminals together?

Shorting all terminals of a winding keeps the whole winding at the same test potential, so the voltage stresses only the insulation between windings and to ground, and inductive kick when testing stops is avoided.

What is a good polarisation index for a dry-type transformer?

A PI well above 1 indicates the reading keeps rising and the insulation is healthy; a PI near or below 1 suggests moisture or contamination. Acceptable values vary by insulation type, so compare with manufacturer guidance and past results.

Can humidity affect the reading on a dry-type transformer?

Strongly. Moisture on exposed coil surfaces lowers insulation resistance. Record ambient humidity, use the guard terminal to separate surface leakage, and consider drying before judging a marginal result.