How to Megger High Voltage Cable

You need to insulation test a medium or high voltage cable before energizing it, after a fault, or as part of maintenance. The method is similar to low-voltage testing, but the stored energy, induced voltage and test voltages make the procedure far stricter.

High voltage cable is tested one core at a time: with the cable isolated, earthed and under a permit to work, the earth is removed from the core under test, the other cores and the metallic screen stay earthed, and a DC insulation tester at a voltage suited to the cable rating, commonly 2.5 kV, 5 kV or 10 kV, is applied between that core and the screen for a timed test. Record the one-minute and ten-minute readings, then discharge the core through the tester and reapply the earth before moving to the next core. This is work for trained, authorized people only, because a charged cable can hold a lethal amount of energy after the test.

What makes high voltage cable different

A medium or high voltage power cable has a central conductor, a layer of solid insulation such as XLPE or EPR, or older paper insulation, and a metallic screen or sheath that is earthed. In service the full phase voltage sits across that insulation, so the insulation resistance test checks the conductor-to-screen path, along with the cable terminations and joints.

Three things set this apart from testing house wiring:

  • Capacitance. A long cable has substantial capacitance between core and screen. It takes time to charge at the test voltage and stores real energy afterwards.
  • Induced voltage. A cable running beside energized circuits can pick up voltage by induction even when isolated. Earths must be applied before work and kept on except during the test itself.
  • Two ends. The far end of the cable may be in another substation or building. It must be isolated, guarded and marked so nobody can touch it while you test.

A DC insulation resistance test is a condition check. It is often paired with a withstand test, usually very low frequency (VLF) AC for modern polymer cables, because high-voltage DC withstand testing is discouraged on some aged XLPE cable.

Choosing the test voltage

Cable rating (phase to phase) Typical insulation resistance test voltage (DC)
Up to 1 kV 500 V to 1 kV
Around 3.3 kV 2.5 kV
6.6 kV to 11 kV 5 kV
Higher distribution and transmission voltages 5 kV to 10 kV or as specified

These are typical maintenance values; the cable owner’s specification, the manufacturer and the relevant standard set the actual voltage. An insulation resistance test is not meant to break down the insulation, so the voltage should stress it meaningfully without approaching a withstand level. Using a much higher voltage on an old cable can push a weak spot to failure during the test.

Step by step on site

  1. Obtain the permit and isolation. The cable is switched out, isolated at both ends, locked and proven dead by an authorized person, and earthed at both ends with approved earthing equipment.
  2. Prepare the terminations. Clean and dry the cable terminations or bushings. Surface leakage across a dirty termination can dominate the reading.
  3. Guard the far end. Barriers, signs and a person or radio contact at the remote end, since that end will be at test voltage.
  4. Connect the tester while the cable is earthed. Earth lead of the tester to the cable screen and main earth; line lead to the core under test. Connect the guard terminal to a ring wrapped around the termination surface if you need to exclude surface leakage.
  5. Remove the earth from the core under test only. The other cores remain earthed, which also tests insulation between phases in a three-core cable.
  6. Apply the test. Run a timed test, typically with readings at thirty seconds, one minute and ten minutes. The reading should rise as the cable charges and absorption current fades.
  7. Discharge. At the end of the test, let the tester discharge the core and watch the voltage fall to near zero. Then reapply the earth to that core.
  8. Repeat for each core, then for the screen or sheath if a sheath test is required. Record ambient temperature and humidity.

Interpreting the readings

Absolute values for cable insulation depend on length, temperature, insulation type and cable size, so there is no universal pass figure. Insulation resistance falls with length, because a longer cable has more insulation in parallel, so results are often normalized to a standard length, such as megohms times kilometres, for comparison with the manufacturer’s values.

  • Compare the cores. Three cores of the same cable should read similarly. One core much lower than the others points to a local defect, such as a damaged joint or a wet termination.
  • Compare with history. A falling trend over successive tests matters more than any single value.
  • Polarization index. The ten-minute reading divided by the one-minute reading. On older paper-insulated cables a value around 2 or more is generally taken as healthy and around 1 as poor. On modern polymer cables, very high resistance can make the ratio less meaningful.
  • Dielectric absorption ratio. The sixty-second reading over the thirty-second reading, a quicker version of the same idea.

Temperature correction is important; insulation resistance falls as temperature rises. For context on low resistance tests that sometimes follow, such as joint resistance with a milliohm meter, and how earth system checks differ, see earth ground testers.

A worked example of length normalization: a 2 km cable reads 1,500 MΩ on one core. Multiplying by the length gives 3,000 MΩ km. If a 500 m section of the same cable type reads 6,000 MΩ, that is also 3,000 MΩ km, so the two are equivalent despite the very different raw readings. Comparing raw megohm values between cables of different lengths, without this step, leads to wrong conclusions.

Safety limits and who should do this

Medium and high voltage cable testing should only be carried out by people trained and authorized under the site’s electrical safety rules, usually with a permit to test or sanction for test. The test voltage is dangerous, and the energy stored in the cable afterwards can be lethal. A cable that has been tested at several kilovolts must be discharged and then earthed, and earths should stay on for a period after the test because the insulation can rebuild a voltage through dielectric absorption.

Never apply a test to a cable that is not proven dead and earthed at both ends beforehand. Never rely on the tester’s live-circuit warning as proof of isolation. If you are a low-voltage electrician without HV authorization, the right action is to engage a qualified testing contractor or the cable owner’s authorized staff. For low-voltage testers and their limits, see insulation resistance testers.

Plan the test before the outage

Before the outage, agree the test voltage and procedure with the cable owner, confirm who controls both ends, and prepare a results sheet with spaces for each core’s thirty-second, one-minute and ten-minute readings plus temperature. Having those numbers recorded the same way each time turns a single test into a trend you can act on.

Frequently Asked Questions

Can I use a 1,000 V handheld tester on an 11 kV cable?

It will give a reading, but it does not stress the insulation enough to be a meaningful condition test for that voltage class. Most specifications call for a 5 kV tester or higher on 11 kV cable.

Why test one core at a time with the others earthed?

Testing one core against the earthed screen and other cores checks both core-to-earth and core-to-core insulation, and it ensures every core not under test stays safe.

What does the guard terminal do on a cable test?

It diverts current that leaks across the surface of a dirty termination away from the measurement. The result then reflects the insulation inside the cable.

How long should a high voltage cable stay earthed after a test?

At least as long as the test, and longer for long cables, because the insulation can rebuild charge. Many procedures leave earths applied until the cable is reconnected.

Is DC testing harmful to XLPE cable?

Routine DC insulation resistance tests at moderate voltage are generally accepted. High-voltage DC withstand testing on aged XLPE cable is discouraged, and VLF AC is usually preferred for withstand tests.