Turn off and lock out the pump circuit, prove it dead, then disconnect the pump motor leads from the control box, pressure switch or controller, and test each lead to the ground wire or a ground rod connection at 500 V DC for about a minute. The reading covers the drop cable, the splice and the motor together, so a good result clears all three, while a very low reading, well under a megohm, usually means damaged cable, a failed splice or a motor winding to ground. Never test through a constant-pressure drive or electronic controller, and pair the insulation test with a winding resistance check to complete the diagnosis.
What you are testing from the top of the well
A submersible pump motor sits at the bottom of the well, sealed and filled with water or oil, connected by a drop cable that runs up beside the pipe, usually with a waterproof splice near the motor. At the surface the cable ends in a control box for three-wire single-phase motors, a pressure switch for two-wire motors, a starter for three-phase motors, or an electronic drive.
When you test from the surface, the tester sees:
- the drop cable insulation along its full length, submerged in water
- the splice at the motor leads, a common failure point
- the motor lead insulation and the winding insulation inside the motor
- the surface wiring if you test before disconnecting it
Because the whole cable is immersed in groundwater, which is effectively earth, any break in the insulation along the way leaks straight to ground. That makes the insulation test very effective at finding cable damage.
The depth matters too. A pump set a long way down has a long drop cable, and every metre of submerged insulation adds a small leakage path in parallel. Two identical installations can give different readings simply because one pump hangs much deeper. That is why the motor maker’s guide tables are written for the motor with its drop cable, and why the best reference for your own pump is its previous reading, taken the same way.
Isolation and set-up
- Lock out the pump circuit at the breaker. Well pumps are often on a dedicated 240 V circuit; confirm which breaker it is.
- Prove dead at the control box or pressure switch with a rated voltage tester.
- Identify the leads. A two-wire single-phase pump has two power leads plus ground. A three-wire pump has three leads, often yellow, black and red, for common, main and start, plus ground. A three-phase pump has three leads plus ground.
- Disconnect the motor leads from the control box, pressure switch or starter, so the surface wiring, capacitors, relays and controls are out of the test. Keep the lead ends apart.
- Never test through an electronic constant-pressure controller or drive. Disconnect the motor leads at its output terminals.
- Find a solid ground. Use the ground wire from the pump or the well casing ground connection, checked for continuity to the electrical system ground.
Running the test and reading the numbers
- Run an open-lead test on the tester first.
- Select 500 V DC, which is the usual test voltage for 230 V and 460 V submersible motors.
- Clip the earth lead to ground and the line lead to the first motor lead. Hold for one minute and record. Repeat for each motor lead.
- Let the tester discharge between tests. A long drop cable has noticeable capacitance.
Submersible motor makers publish guide tables for readings from the surface with the drop cable connected, and you should check the table for your motor. As a general picture of how those tables run:
| Lead to ground, with drop cable | General interpretation |
|---|---|
| Several megohms or more | Good insulation, typical of a new or healthy installation |
| Roughly 0.5 to a few megohms | Used motor and cable in acceptable condition; note it and test again later |
| Below about 0.5 MΩ | Insulation damage in cable, splice or motor; locate and repair |
| Near zero | Direct ground fault; pump must be pulled |
A motor tested on its own, out of the well and without cable, should read far higher, typically tens of megohms or more. Readings with cable are lower because a long, submerged cable leaks more in total. The Srliya digital insulation tester is one installation-style option, but confirm that whichever tester you use offers a 500 V insulation range; the guide to insulation resistance testers covers others.
Winding resistance: the second half of the diagnosis
An insulation test shows leakage to ground, but a pump can fail with good insulation and a broken or shorted winding. Measure resistance between the motor leads with the leads still disconnected:
- Two-wire pump: one resistance between the two leads.
- Three-wire pump: yellow to black (main winding), yellow to red (start winding) and black to red, which should equal the sum of the other two.
- Three-phase pump: all three pairs should read equal.
Compare with the motor maker’s values for the motor’s horsepower and voltage, adding the resistance of the drop cable for its length and gauge. An open reading means a broken cable, failed splice or open winding. A reading well below specification suggests shorted turns. A multifunction tester such as the Kyoritsu KEW 6010B provides both the insulation and low-resistance ranges. For very low winding values on bigger motors, see milliohm meters for low resistance testing; the difference between the two checks is set out in insulation tester versus continuity test.
When to pull the pump, and who should do it
A grounded pump on a circuit with poor grounding can energize the well casing, plumbing and the water itself. If insulation reads near zero, leave the pump off and do not reset the breaker repeatedly. Repeated restarts into a ground fault can also damage the control box and wiring.
Pulling a submersible pump means lifting a heavy string of pipe, cable and motor out of the well, with a risk of dropping it down the hole. That is a job for a licensed well or pump contractor. They can test the motor on its own at the surface, repair or replace the splice, and decide whether the cable or the motor is at fault. Electrical work on the supply, breaker and control box belongs to a licensed electrician where local rules require it.
Record readings for the contractor
Write down the insulation reading for each lead, the resistance between each pair of leads, the motor horsepower and voltage, and the approximate depth of the pump. Handing those numbers to a well contractor usually tells them before they arrive whether they are coming to fix a splice, replace cable or change the motor.
Frequently Asked Questions
Can I megger a submersible pump without pulling it?
Yes, testing from the surface with the leads disconnected at the control box is the normal first step. The result covers cable, splice and motor together.
Why is my reading lower than a dry motor would read?
The drop cable is submerged in water and adds leakage along its whole length. Readings with cable are always lower than for the motor alone, which is why maker tables list them separately.
What voltage should I use to megger a well pump?
500 V DC is the usual choice for 230 V and 460 V submersible motors. Follow the motor maker's instructions where they differ.
Can a bad splice cause a low megger reading?
Yes, and it is one of the most common causes. Water entering a poorly made splice near the motor gives a low reading that looks like a motor fault until the pump is pulled.
Should I megger through the control box?
No. Disconnect the motor leads from the control box first. Capacitors, relays and any electronics in it would distort the reading and could be damaged.