Switch off and lock the main switch, prove the circuits dead, unplug every appliance, remove lamps and disconnect electronic devices such as dimmers, smart switches, timers and surge protectors. Then test each circuit at 500 V DC between line and neutral, line and earth, and neutral and earth, or with line and neutral joined and tested together to earth. Under BS 7671 the minimum for a 230 V circuit is 1 MΩ, but healthy wiring usually reads hundreds of megohms, so any circuit far below its neighbours deserves investigation by an electrician.
What the test tells you about your wiring
Insulation testing applies a DC voltage between conductors that should never touch and measures the leakage current. On a house circuit that means three pairs: line to neutral, line to earth and neutral to earth. Good PVC or rubber insulation in dry conditions leaks almost nothing, so readings are high, often over the meter’s range.
Low readings show up where something has gone wrong: a nail or screw through a cable, a crushed cable behind a skirting board, water in an outdoor socket or junction box, rodent damage, heat-damaged insulation around light fittings, or old rubber insulation that has gone brittle. A low neutral-to-earth reading is a frequent cause of RCD or GFCI tripping, because that protection compares current in line and neutral and any neutral leakage to earth upsets the balance.
In the UK and many IEC countries, insulation testing is a required part of initial verification and periodic inspection. In the US it is not a routine requirement for dwelling wiring, but electricians use it for fault-finding and on older homes. The method is the same either way.
Prepare the installation first
- Isolate the supply. Switch off the main switch, lock it off if possible, and remove the key or label it. If there are other sources, such as a generator or battery system, isolate them too.
- Prove dead at the distribution board and at a socket on each circuit with a rated voltage tester, proven on a known live source before and after.
- Remove loads. Unplug everything from sockets. Remove lamps from lighting circuits so they do not bridge line and neutral. Disconnect fixed appliances at their spurs.
- Disconnect electronics. Dimmers, smart switches, electronic timers, fan controllers, doorbell transformers, smoke alarms on mains, and surge protective devices in the board. These can be damaged by 500 V and will skew the reading.
- Deal with RCDs and electronic breakers. Some combined RCBOs and AFCIs contain electronics; follow the maker’s instructions, often testing with the device off and the outgoing conductors disconnected.
- Switch light switches on during line tests so the switched lines are included, if lamps have been removed.
Running the test circuit by circuit
- Open-lead test on the tester: separated leads should read over-range. Short the leads: zero.
- Select 500 V DC, the standard voltage for 230 V and 120/240 V circuits.
- At the board, with the circuit breaker off or the circuit disconnected, test:
- line to neutral
- line to earth
- neutral to earth
Alternatively, join line and neutral together and test them to earth in one go, which is gentler on any devices you could not disconnect.
- Hold each test until the reading settles, usually a few seconds on house circuits, and record it.
- Let the tester discharge before moving the leads.
- Repeat for every circuit. You can test the whole installation at once from the main switch with all breakers on, then split down if the overall reading is low.
- Reconnect everything you disconnected, restore power and test RCD or GFCI operation.
A multifunction tester such as the Kyoritsu KEW 6010B covers continuity, insulation, loop and RCD tests in one instrument, which is the full set an electrician uses on house wiring; the Srliya insulation, loop and RCD tester combines insulation with loop and RCD checks.
What the readings mean
| Reading at 500 V DC | What it usually means | Action |
|---|---|---|
| Over-range or hundreds of megohms | Healthy, dry insulation | None |
| Tens of megohms | Acceptable; normal on large or older installations | Note it and compare at the next inspection |
| Between 1 and 2 MΩ | Passes the BS 7671 minimum but low | Test circuits individually, look for damp or damage |
| Below 1 MΩ | Fails the minimum for a 230 V circuit | Do not energize the circuit until the fault is found |
| Near zero | Direct fault: conductors touching or a nail through a cable | Locate and repair before use |
A whole-house reading is all circuits in parallel, so it is always lower than any single circuit. A house with twenty circuits each at 200 MΩ will read about 10 MΩ overall. If one circuit reads far lower than the others, that is your problem circuit even if it technically passes.
If a circuit reads low, check that nothing was left plugged in before suspecting the cable. A forgotten appliance or lamp is the most common reason. Insulation is a different measurement from continuity of the earth path, which is checked separately, as explained in insulation tester versus continuity test. Earth electrode resistance at the property is another separate test, covered in earth ground testers.
The arithmetic behind that parallel effect is simple: for identical circuits, divide one circuit’s reading by the number of circuits. Two circuits at 100 MΩ give 50 MΩ together, four give 25 MΩ, and ten give 10 MΩ. So an overall reading of 3 MΩ on a ten-circuit board is not alarming on its own, but if nine circuits read 200 MΩ and one reads 3 MΩ, that one circuit is almost certainly where the leakage is.
Safety limits and when to call an electrician
This test is done on dead circuits, and the danger is mostly in isolation going wrong: borrowed neutrals, mislabelled boards, a second supply or someone switching the power back on. The tester’s own output can give a sharp shock, so keep hands off the conductors and warn others in the house during the test.
In many countries, testing and certification of house wiring must be done by a registered or licensed electrician, and DIY work on fixed wiring is restricted. If your RCD or GFCI keeps tripping, you can unplug appliances one by one to find a faulty appliance yourself, but once the fault is in the fixed wiring, call an electrician. Signs that need urgent attention include burning smells, scorched sockets, buzzing or a circuit that reads near zero. For choosing an insulation tester for professional work, see insulation resistance testers.
Start with the circuit that trips
If an RCD or GFCI is tripping, unplug every appliance on that circuit first and see if it still trips; if it does, have the circuit insulation tested from line and neutral to earth at 500 V DC with all loads removed. Compare its reading with the other circuits on the board, and the odd one out shows where the electrician should start looking.
Frequently Asked Questions
Can I megger house wiring with everything plugged in?
You should not. Appliances and electronics will pull the reading down and some can be damaged. Unplug and disconnect them first.
What is a good megger reading for house wiring?
Healthy wiring at 500 V DC usually reads hundreds of megohms or over-range. The minimum under BS 7671 for a 230 V circuit is 1 MΩ, but anything far below the other circuits is worth investigating.
Why does my whole-house reading look so low?
All circuits are in parallel when tested together, so their leakage adds up. Test each circuit separately to see the real values.
Do I need to remove light bulbs to megger lighting circuits?
For line-to-neutral tests, yes, because a lamp connects line to neutral. For line and neutral joined together to earth, lamps can stay, but electronic drivers and dimmers are better disconnected.
Can I megger wiring with the RCD in circuit?
Follow the device maker's instructions. Many electronic RCDs and RCBOs should be switched off or disconnected, since the test can damage their electronics or give false readings.