How to Megger Test a DC Motor

A DC motor is tripping its drive, smells hot, or is due for a maintenance check, and you need to know whether the windings are still insulated. This is the procedure, from lockout to discharge.

As an Amazon Associate, Akermin earns from qualifying purchases. Product links on this page are affiliate links.

Lock out the supply, disconnect the motor leads from the drive or starter, and connect the insulation tester between the armature lead (A1 or A2) and a clean bare point on the frame, then between the field leads (F1 and F2, plus S1 and S2 on a compound motor) and the frame, and finally between armature and field. For motors rated up to roughly 600 V, a 500 V DC test is the usual choice; hold it for one minute and record the reading and the winding temperature. Healthy windings typically read in the hundreds of megohms or more, and anything in the low single megohms needs cleaning, drying or rewinding before the motor goes back into service. Discharge each winding to the frame after every test.

What the test is measuring in a DC motor

A DC motor has at least two separate circuits: the armature, reached through the brushes and commutator, and one or more field windings on the stator poles. A shunt motor has a field across the supply, a series motor has a field in series with the armature, and a compound motor has both. Each circuit should be insulated from the steel frame and from the other circuits.

An insulation resistance tester, often called a megger after an early brand, pushes a steady DC voltage of 250, 500 or 1000 V across that insulation and measures the tiny current that leaks through it. Dividing voltage by current gives a resistance in megohms. A multimeter cannot do this job, because its ohms range uses only a few volts and will show OL on insulation that breaks down under working voltage. The difference is covered in insulation testing versus a continuity test.

DC motors have a particular weakness: carbon dust from the brushes. It settles on the brush rigging, the commutator risers and the end windings, and it conducts. A large share of low readings on DC machines are caused by dirt rather than by failed winding insulation, which is good news, because dirt can be cleaned.

Before you connect the tester

  1. Isolate and lock out. Open the disconnect, apply your lock and tag, and prove dead at the motor terminals with a voltage tester you have checked on a known live source.
  2. Disconnect the motor from the drive. SCR and PWM drives, field supplies, surge suppressors and tachogenerators can be damaged by the test voltage, and they also give false low readings. Lift the motor leads in the terminal box and keep them apart.
  3. Identify the leads. A1 and A2 are armature, F1 and F2 shunt field, S1 and S2 series field. On some motors the interpole and compensating windings are connected internally in the armature circuit.
  4. Find a clean frame connection. Scrape paint from a frame bolt or use the motor’s earth terminal. A poor earth clip gives an optimistic high reading.
  5. Note the temperature. Insulation resistance falls sharply as windings warm up; a commonly used approximation is that it roughly halves for every 10 C rise. Record winding or ambient temperature so readings can be compared over time.

The test sequence

Choose the test voltage from the motor’s rating. A common practice is 500 V DC for motors rated up to about 600 V and 1000 V DC for higher voltage machines; small motors on low voltage battery systems are often tested at 250 V. Check the motor or plant specification if one exists.

  1. Armature to frame. Line lead on A1, earth lead on frame. The brushes connect A1 through the commutator to every armature coil, so one lead tests the whole armature. Apply for 60 seconds and record the reading.
  2. Shunt field to frame. Line lead on F1, earth on frame. Record after 60 seconds.
  3. Series field to frame, if fitted, on S1.
  4. Armature to field. Line lead on A1, earth lead on F1. A low reading here with good readings to frame points to contamination or damage between circuits, often at the brush gear.
  5. Discharge. Most testers discharge automatically when you release the test button, but short each winding to frame with a discharge lead before you touch it, for several times as long as the test voltage was applied; four times the test duration is a common rule. A large motor holds a charge that can give a nasty shock.
  6. Optional polarization index. Repeat the armature test for ten minutes and divide the ten minute reading by the one minute reading. A ratio above about 2 suggests clean, dry insulation; a ratio near 1 suggests moisture or contamination.

Testers with timed tests and stored results make this tidier. A multifunction instrument such as the Kyoritsu KEW 6010B covers insulation alongside other installation tests, and the wider choice is in insulation resistance testers.

Reading the results

One minute reading, temperature corrected Likely condition Action
Hundreds to thousands of megohms Good, clean insulation Record as a baseline and return to service
Tens of megohms Acceptable but watch the trend Clean brush gear, compare with past readings
A few megohms Contaminated or damp, near the usual minimum for low voltage windings Clean carbon dust, dry the windings, retest
Below about one megohm Poor insulation Do not energize; clean and dry, then rewind if it does not recover
Near zero, or test voltage collapses Winding grounded to frame Motor needs repair or rewinding

The trend matters as much as the number. A motor that read two thousand megohms at its last check and 40 today has changed, even though 40 still passes. Always compare at a similar temperature and the same test voltage.

If the armature reads low, lift the brushes off the commutator and test the brush rigging to frame on its own. If the rigging is now low and the armature, tested by touching a probe to a commutator bar, is high, the problem is dust on the brush holders, not the windings.

Insulation is only half the picture

A motor can pass a megger test and still be faulty. Shorted turns inside a field coil, an open armature coil or a burnt commutator bar are all internal to the copper and invisible to an insulation test. For those you need resistance measurements: compare the two halves of a field, check the field against its nameplate or a sister motor, and run a bar-to-bar test around the commutator. Those resistances are often fractions of an ohm, below what most multimeters resolve well, which is where a 4-wire instrument such as a milliohm meter for low resistance testing earns its place.

Safety limits: insulation testers produce lethal voltages, and a large armature stores charge. Never test a motor that is still connected to a drive or to other people’s equipment, never touch leads during a test, and do not test in an explosive atmosphere unless the instrument and permit allow it. Motors that read near zero, or that have been flooded, should go to a qualified motor repair shop rather than be dried and restarted on guesswork.

Record a baseline today

Run the four tests, write down each one minute reading with the winding temperature and test voltage, and tape the sheet inside the terminal box lid. Next time the motor trips you will be comparing against its own history rather than guessing from a generic table.

Frequently Asked Questions

Can I megger a DC motor without disconnecting it from the drive?

You should not. The test voltage can destroy drive electronics, and the drive's internal circuits also leak current that makes the motor look worse than it is. Lift the motor leads first.

What voltage should I megger a 24 V or 90 V DC motor at?

Low voltage motors are commonly tested at 250 V, and 500 V is the usual general figure for windings rated under about 1000 V. Using a far higher voltage than the insulation is built for can stress it unnecessarily, so use the manufacturer's test voltage if one is given, and lean toward the lower setting on small motors.

Why did the reading go up after I cleaned the brush gear?

Carbon dust from the brushes is conductive and gives a leakage path to frame. Removing it eliminates that path, so the reading rises toward the true insulation value of the windings.

How do I dry a damp DC motor?

Gentle heat over several hours, such as a warm room, low temperature oven in a repair shop, or a controlled low current through the windings, is the usual approach. Retest as it dries and expect the reading to rise steadily.

Is a polarization index test needed on small motors?

Not usually. It is most informative on larger machines. For small DC motors, a one minute reading compared with past readings at similar temperature is generally enough.