The quickest field check is a standing pressure-temperature test: let the cylinder or idle system settle at a stable temperature for several hours, read the pressure, and compare it with the PT chart for that refrigerant. Pressure noticeably higher than the chart usually means air or another refrigerant is mixed in; a refrigerant identifier confirms the blend and purity in a minute or two. Moisture and acid need separate checks, a moisture indicator on the liquid line and an acid test of the oil. Contaminated refrigerant should not be recharged into a system; it goes to a reclaimer.
The four kinds of contamination and why they matter
Refrigerant in the field gets contaminated in a handful of predictable ways. Each harms the system differently, so it is worth knowing which you are looking for:
- Mixed refrigerants. Someone topped up R-22 with a drop-in, or recovered two different gases into one cylinder. The mixture has its own pressure-temperature relationship, so the charge, superheat and subcooling targets no longer apply, and oil compatibility can be wrong.
- Non-condensables, mostly air and nitrogen. These enter through poor evacuation, leaks on the low side running in vacuum, or careless recovery. They collect in the condenser, raise head pressure and reduce capacity.
- Moisture. Water reacts with refrigerant and oil to form acids, freezes at metering devices, and turns polyolester oil acidic quickly.
- Acid and burnout products. After a compressor motor burns out, the refrigerant and oil carry acids, carbon and sludge that will destroy a replacement compressor if not cleaned out.
None of these show up on a leak detector. Tools such as heated diode or infrared sniffers react to refrigerant escaping, not to its purity. The overview of what a refrigerant leak detector does explains the limits.
Standing pressure-temperature test, step by step
A pure refrigerant, or a near-azeotropic blend, sitting with liquid present in a closed container has a pressure set only by its temperature. That makes it an easy purity screen.
- Let it settle. Leave the cylinder, or the system switched off, in one place with stable surroundings for several hours, ideally overnight, so the liquid reaches the room temperature. Keep it out of sun and away from heaters.
- Measure the liquid temperature, not the air. Tape a thermometer probe to the cylinder wall near the bottom and insulate over it.
- Read the pressure with an accurate gauge or digital manifold on the vapour port.
- Compare with the PT chart for the labelled refrigerant at that temperature. At 70 F (about 21 C), for example, R-134a sits around 71 psig, R-22 around 121 psig and R-410A around 201 psig.
- Interpret the gap. A few psi either way is normal given gauge and thermometer accuracy. Well above the chart suggests non-condensables or a higher-pressure gas mixed in. Well below suggests a lower-pressure gas mixed in, or that there is no liquid left in the container.
Zeotropic blends with large glide, such as R-407C, can be harder to judge this way, because partial leaks change their composition. Use the bubble-point value from the chart, and lean on an identifier for these.
| What you find | Most likely meaning | Next step |
|---|---|---|
| Pressure matches chart within a few psi | Probably pure and air-free | Confirm with identifier if history is unknown |
| Pressure well above chart | Air, nitrogen or a higher-pressure refrigerant | Run identifier; do not reuse until confirmed |
| Pressure well below chart | Lower-pressure refrigerant mixed in, or vapour only | Check weight and identifier |
| Moisture indicator shows wet | Water in the system | Replace drier, deep evacuate, check oil acid |
| Oil dark, smells burnt, acid test positive | Burnout or heavy acid | Burnout clean-up procedure, suction filter drier |
Using a refrigerant identifier
An identifier draws a small vapour sample through a filter into a non-dispersive infrared bench and reports the composition, typically the percentage of the expected refrigerant, the presence of other common refrigerants and hydrocarbons, and air. Many also flag a blend of unknowns as contaminated.
- Always sample vapour, and use the filter supplied; liquid or oil in the sample line damages the bench.
- Let the unit warm up and calibrate to fresh air as instructed.
- Pay attention to hydrocarbon warnings. Some illegal or unlabelled top-up products contain propane or isobutane, which makes the refrigerant flammable and dangerous to recover with standard equipment.
- Purity well below what the reclaimer accepts means the gas is for reclaim only.
Reclaimed refrigerant sold for reuse is held to a purity specification, AHRI 700 in North America. You do not need lab equipment to reach a decision on site; the identifier tells you whether to reuse, recover separately, or treat as mixed waste.
Checking for moisture and acid
- Look at the sight glass and moisture indicator on the liquid line if the system has one. The indicator changes colour when moisture is present; compare with the chart printed on it, and give it time after the system starts, since it needs flow to read correctly.
- Run an acid test on the oil. Take a small oil sample from the compressor or a suction access point with an oil test kit; the reagent changes colour when acid is present. Use a kit that matches the oil type, mineral, alkylbenzene or POE.
- Inspect the oil itself. Clean oil is clear and light. Dark, cloudy or gritty oil, especially with a sharp burnt odour, points to a burnout.
- Use acid test kits for refrigerant too, where available, which bubble a vapour sample through an indicator.
- Check the filter drier for restriction. A noticeable temperature drop across the liquid-line drier suggests it is clogged with debris or sludge and due for replacement; a drier can be saturated with moisture without showing any drop, so this does not replace the moisture indicator.
What to do with contaminated refrigerant, and safety limits
Do not vent it. In most countries, releasing refrigerant on purpose is illegal, and in the United States handling it requires EPA Section 608 certification. Recover contaminated refrigerant into a dedicated, clearly labelled recovery cylinder, never into one holding clean gas of the same type, and send it to a reclaimer. Mixed or hydrocarbon-contaminated gas must be labelled as such.
Treat the system as well as the gas. After a burnout, fit suction and liquid-line filter driers rated for acid removal, change the oil if the compressor maker requires it, check the oil acid again after a period of running, and evacuate to a deep vacuum with a micron gauge to remove moisture and air. Then charge with new or reclaimed refrigerant by weight.
Safety: refrigerant displaces oxygen in confined spaces, and exposed to flame or very hot surfaces it can decompose into toxic, corrosive gases. Wear eye protection and gloves when handling liquid refrigerant, which causes frostbite. A2L and A3 refrigerants are flammable, and recovery machines and leak detectors must be rated for them; the guide to A2L refrigerant leak detectors covers the detection side. If a cylinder’s label and contents disagree and you are not certified, hand it to a licensed technician.
Once the system is recharged, a sensitive detector such as the Elitech ILD-200 infrared leak detector helps you find whatever let the air or moisture in. Before relying on it, test the leak detector on a known reference.
Start with the overnight PT check
If you are unsure about a cylinder, leave it in a stable room overnight, tape a probe to its side under insulation, and compare its pressure with the PT chart in the morning. A clear match is reassuring; any significant gap means it goes through an identifier, and if it fails there, it is recovered separately and sent for reclaim rather than charged into anyone’s system.
Frequently Asked Questions
Can you smell contaminated refrigerant?
Not reliably. Most refrigerants have little odour, and a sharp burnt smell is more likely from burnt compressor oil than the refrigerant. Use pressure, identifier and acid tests rather than your nose.
Does air in the refrigerant cause high head pressure?
Yes. Non-condensables gather in the condenser, take up space that refrigerant should condense in, and raise head pressure and discharge temperature while reducing cooling.
Can contaminated refrigerant be cleaned on site?
Recovery machines with filter driers remove some moisture and particles, but they cannot separate mixed refrigerants. Mixed gas has to be reclaimed by a facility or destroyed.
Is a refrigerant identifier necessary?
For routine work on known systems, many technicians rely on PT checks. When a system's history is unknown, a hydrocarbon contaminant is possible, or you are buying recovered gas, an identifier is the only quick way to be sure.
What does a wet moisture indicator mean?
Water has entered the system. Replace the filter drier, find how the moisture got in, evacuate thoroughly, and test the oil for acid before returning the system to service.