Yes, a psychrometric chart shows dew point, though usually not as its own labelled axis. Find your air’s state point from dry-bulb temperature and relative humidity, then move horizontally to the left until you meet the curved saturation line, the 100 percent humidity edge of the chart; the temperature at that point is the dew point. Horizontal lines on the chart are lines of constant moisture content, and every point on one line shares the same dew point.
Why a horizontal line is a dew point line
A psychrometric chart plots dry-bulb temperature along the bottom and humidity ratio, the mass of water vapour per mass of dry air, up the right-hand side. The curved upper-left edge is the saturation curve, where relative humidity is 100 percent. Other curves inside the chart show lower relative humidities, and sloping lines show wet-bulb temperature and enthalpy.
Dew point is the temperature at which air would become saturated if cooled without adding or removing water. Cooling air without changing its moisture content means moving left at constant humidity ratio, which on the chart is a horizontal line. Keep moving left and you eventually hit the saturation curve. Water starts to condense there. The temperature at that point is the dew point.
So the dew point depends only on the humidity ratio, the height on the chart, and not on the dry-bulb temperature. Many charts print the dew point scale along the saturation curve itself, or let you read it on the dry-bulb axis below the intersection. For the wider meaning of the number, see what dew point means indoors.
Because of this, dew point is often the most useful single moisture number for HVAC work. Relative humidity changes every time the air heats or cools, but dew point stays fixed until moisture is actually added, by people, cooking, showers or damp ground, or removed, by a cooling coil or dehumidifier. Tracking dew point across a cooling coil, for instance, tells you directly how much water the coil is pulling out of the air.
Reading it step by step
- Find the dry-bulb temperature on the horizontal axis and follow the vertical line up.
- Find the relative humidity curve that matches your reading. Where the vertical line crosses it is your state point. If you have wet-bulb temperature instead of relative humidity, follow the sloping wet-bulb line from the saturation curve down to meet the dry-bulb line.
- Move horizontally to the left from the state point, keeping the humidity ratio constant.
- Stop at the saturation curve. This is the 100 percent relative humidity edge.
- Read the temperature there. Either from the scale printed along the curve, or by dropping straight down to the dry-bulb axis. That is the dew point.
Worked example: air at 24 °C and 50 percent relative humidity. The state point sits at a humidity ratio of a little under 0.0094 kg of water per kg of dry air. Moving left, you reach the saturation curve at about 13 °C. A calculation with the Magnus approximation gives 12.9 °C, so the chart reading agrees. In Fahrenheit, 75 °F at 50 percent gives a dew point of about 55 °F.
Second example: 20 °C at 60 percent relative humidity. The horizontal line meets saturation at about 12 °C. If any surface in that room is colder than 12 °C, such as a single-glazed window on a cold night or an uninsulated cold water pipe, condensation will form on it.
Quick reference at common conditions
The table gives approximate dew points at sea-level pressure, the same values you would read from a standard chart. They are rounded to the nearest degree.
| Dry bulb | 30 percent RH | 50 percent RH | 70 percent RH |
|---|---|---|---|
| 15 °C | about -2 °C | about 5 °C | about 10 °C |
| 20 °C | about 2 °C | about 9 °C | about 14 °C |
| 24 °C | about 5 °C | about 13 °C | about 18 °C |
| 28 °C | about 9 °C | about 17 °C | about 22 °C |
Notice how the gap between dry bulb and dew point narrows as humidity rises. At 70 percent the dew point is only a few degrees below room temperature, which is why humid rooms sweat on windows and pipes so readily. To calculate these values yourself instead of reading a chart, see calculating dew point from temperature and humidity.
Mistakes that give the wrong dew point
- Following a wet-bulb line instead of a horizontal line. Wet-bulb lines slope down to the right. They meet the saturation curve at the wet-bulb temperature, which is always between the dew point and the dry bulb. Confusing the two gives a dew point that is too high.
- Reading the wrong relative humidity curve. The curves are close together near the bottom of the chart. Count them carefully or use a ruler.
- Using a chart for the wrong pressure. Standard charts assume sea-level pressure. At high altitude, special charts apply; for home use the error is small, but for engineering work at elevation it matters.
- Inaccurate input readings. A hygrometer that reads 5 points high shifts the dew point by roughly a degree or more at typical room conditions. The chart can only be as good as your measurement.
- Mixing units. Some charts are in Fahrenheit with grains of moisture per pound of dry air, others in Celsius with grams per kilogram. Use one chart consistently.
Getting good inputs and skipping the chart
The most reliable inputs come from a sling or digital psychrometer, which measures both dry-bulb and wet-bulb temperature, the two values the chart was designed around. The method is described in how to use a psychrometer. A digital unit such as the ERAY digital psychrometer displays wet-bulb and dew point directly, so you can use it to check your chart reading.
Many thermo-hygrometers also calculate dew point for you. The ALLOSUN thermometer hygrometer shows temperature, relative humidity and dew point together, which is handy for checking whether a basement or cold wall is near condensation. For logging over days, a recorder like the Elitech data logger stores temperature and humidity so you can work out dew point across a whole cycle.
To confirm a hygrometer before trusting a dew point from it, run a salt test: a sealed container with damp table salt settles near 75 percent relative humidity at room temperature. If your instrument is off, correct the reading before using the chart. When a dew point reading shows a surface will regularly be colder than the air’s dew point, the fix is either to reduce indoor humidity, warm the surface, or insulate it.
Try it on your own room
Take a temperature and humidity reading in the room that worries you, plot the point on your chart, slide horizontally to the saturation curve, and then measure the coldest surface in that room with a probe or infrared thermometer; if that surface is at or below the dew point you found, you have located your condensation problem.
Frequently Asked Questions
What is the difference between wet-bulb and dew point on the chart?
Wet-bulb is found by following the sloping wet-bulb line to the saturation curve, while dew point is found by moving horizontally. Wet-bulb is always equal to or higher than dew point and equal to or lower than dry bulb.
Can dew point ever be higher than air temperature?
No. At saturation the dew point equals the air temperature, and at lower humidity it is below it. If a reading suggests otherwise, one of the input measurements is wrong.
Why does my chart have no dew point axis?
Many charts mark dew point along the saturation curve rather than as a separate axis, because dew point and humidity ratio are directly linked. Read it where your horizontal line meets the curve.
Is reading a chart accurate enough for HVAC work?
For most field work, yes, within a degree or so, provided your inputs are accurate and the chart matches your altitude. Software and digital psychrometers give more precise values when needed.
Does dew point change if I heat a room?
Not by heating alone. Heating raises dry-bulb temperature and lowers relative humidity, but the moisture content stays the same, so the dew point stays put. Adding or removing water changes it.