120.4

How to Megger House Wiring

House wiring is meggered with the supply isolated and all loads and electronics disconnected, by testing line, neutral and earth against each other at 500 V DC and comparing each circuit with the minimum and with its neighbours.

Read More→
120.4

How to Megger High Voltage Cable

High voltage cable is insulation tested by isolating and earthing it under a permit, removing earths from one core at a time, applying a DC test voltage of several kilovolts between that core and the screen, recording timed readings, then discharging and re-earthing.

Read More→
120.4

How to Megger a Submersible Pump

A submersible pump is meggered from the surface by isolating the supply, disconnecting the pump leads at the control box or pressure switch, and testing each lead to ground at 500 V DC, remembering the reading covers both the drop cable and the motor.

Read More→
120.4

How to Megger a 3 Phase Compressor

To megger a three-phase compressor, isolate and lock out, remove the leads from the terminals, test each terminal to the compressor shell at 500 V DC, and compare the readings against the manufacturer's minimum and any previous results.

Read More→
120.4

How to Fix Multimeter Test Leads

Most test lead faults are a broken copper strand near the plug or probe, which you find by flexing the lead on the ohms range; low-voltage hobby leads can be repaired, mains-rated leads should be replaced.

Read More→